York E1FB180 Installation Instructions Manual

Split-system heat pumps outdoor units

Advertisement

INSTALLATION INSTRUCTION

GENERAL
The outdoor units are completely piped and wired at the fac-
tory and are shipped ready for immediate installation. Only
the interconnecting liquid and suction lines, sight glasses,
control wiring, and the main power wiring are required to
complete the installation. Every unit is dehydrated, evacu-
ated, leak tested and pressure tested at 450 psig before be-
ing pressurized with a holding charge of refrigerant-22 for
shipment and/or storage.
To eliminate the costly cabinet deterioration problems usually
associated with outdoor equipment, all sheet metal parts are
constructed of commercial grade (G90) galvanized steel. Af-
ter fabrication, each part is thoroughly cleaned to remove
any grease or dirt from its surfaces. The parts that will be
exposed to the weather are then coated with a "desert sand"
powder paint to assure a quality finish for many years. This
coating system has passed the 750-hour, salt spray test per
Every unit includes 2 heavy-duty scroll compressors, 2 suc-
tion line accumulators, 2 4-way reversing valves with a 24
volt solenoid, 2 outdoor fan motors with inherent protection,
and a copper tube/aluminum fin coil that is positioned verti-
cally for better drainage of the water that will condense on it
during the heating cycle.
They also include 2 filter driers, 2 expansion valves and dis-
tributors that are only used during the heating cycle plus a
check valve to provide the proper flow of refrigerant through
the unit during both the cooling and heating cycles.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make
installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal
injury and/or equipment damage may result if installation procedure is not handled properly.
®
Supersedes: 035-16192-000 (0601)
MODELS E1FB180 & E1FB240
ASTM Standard B117.
SPLIT-SYSTEM HEAT PUMPS

OUTDOOR UNITS

O
O
O
O
O
All controls are located in the front of the unit and are readily
accessible for maintenance, adjustment and service. All wir-
ing (Power and Control) can be made through the front of
REFERENCE
This instruction covers the installation and operation of the ba-
sic condensing unit. For information on the installation and op-
eration of the matching indoor units, refer to Installation
Instruction part no. 035-16626-000 (form 515.41-N4Y).
All accessories come with a separate Installation Manual.
Refer to Parts Manual for complete listing of replacement parts
on this equipment.
All forms may be ordered from:
Standard Register
Norman, OK 73069
Toll Free: Tel. 877-318-9675/Fax. 877-379-7920

INSPECTION

As soon as a unit is received, it should be inspected for pos-
sible damage during transit. If damage is evident, the extent
of the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should
be made in writing.
035-16192-001-A-1001
O
O
O
O
O
the unit.

Advertisement

Table of Contents
loading

Summary of Contents for York E1FB180

  • Page 1: General Reference

    SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS Supersedes: 035-16192-000 (0601) MODELS E1FB180 & E1FB240 All controls are located in the front of the unit and are readily accessible for maintenance, adjustment and service. All wir- ing (Power and Control) can be made through the front of...
  • Page 2: Table Of Contents

    035-16192-001-A-1001 GENERAL ... 1 REFERENCE ... 1 INSPECTION ... 1 NOMENCLATURE... 2 INSTALLATION LIMITATIONS ... 3 LOCATION Roof-Top Locations... 3 Ground Level Locations... 3 RIGGING AND HANDLING ... 3 CLEARANCES ... 4 COMPRESSOR CRANKCASE HEATER ... 4 POWER AND CONTROL WIRING Power Wiring ...
  • Page 3: Installation

    LIMITATIONS These units must be installed in accordance with all national and local safety codes. If no local codes apply, installation must conform with the appropriate national codes. See Table 1 for unit application data. Units are designed to meet National Safety Code Standards.
  • Page 4: Clearances

    035-16192-001-A-1001 CAUTION: LENGTH OF FORKS MUST BE A MINIMUM OF 54" (when lifting from the compressor end of the unit) and a MINIMUM OF 42" (when lifting from the front or rear of the unit). Remove the nesting brackets from the four corners on top of the unit.
  • Page 5: Typical Field Wiring

    TERMINALS ON HEAT PUMP THERMOSTAT WIRE IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES FIG. 3 - TYPICAL FIELD WIRING TABLE 3 - ELECTRICAL DATA Maximum fuse or maximum circuit breaker (HACR type per NEC). Based on three 75°C insulated copper conductors in conduit and ambient of 30°C. Based on 5% voltage drop, since unit controls are powered off the unit supply.
  • Page 6: Unit Dimensions & Clearances

    035-16192-001-A-1001 Dim. (in.) Unit 15 Ton 20 Ton All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. FIG. 4 - UNIT DIMENSIONS AND CLEARANCES CENTER OF GRAVITY Connection Size Connection Entry 15 Ton 20 Ton...
  • Page 7: Refrigerant Piping

    TABLE 4 - SUCTION LINES Model Designation System 1 System 2 System 1 System 2 All horizontal suction lines should be pitched at least 1 inch every 20 feet in the direction of the refrigerant flow to aid the return of oil to the compressor. Every vertical suction riser greater than 25 feet in height should have a “P”...
  • Page 8: Liquid Lines

    035-16192-001-A-1001 TABLE 5 - LIQUID LINES Model Designation System 1 System 2 System 1 System 2 Based on Refrigerant-22 at the nominal capacity of the condensing unit, a liquid temperature of 105°F and a suction temperature of 40°F. These friction losses do not include any allowances for a strainer, filter-drier, solenoid valve, isolation valve or fittings. The total pressure drop of the liquid line for both friction and vertical rise must not exceed 40 PSI.
  • Page 9: Extending The Service Ports

    4. After the disc has been removed, burnish the external sur- faces and clean the internal surfaces as outlined above. 5. Move the dry nitrogen supply back to the access port on the liquid line service valve. 6. Braze the liquid line to the liquid connection on the indoor unit while maintaining a minimum flow of dry nitrogen through the liquid line, the indoor coil and the hole in the vapor disc.
  • Page 10: Alternate Charging Methods

    035-16192-001-A-1001 FIG. 5 - EXTENDING THE SERVICE PORTS ALTERNATE CHARGING METHODS If you are starting a unit when the ambient temperature is higher or lower than those shown in Figures 7 through 15, either of the following methods may be used. Method 1: Determine the total weight of the refrigerant for the total system by adding the required charge for the outdoor unit, the indoor unit and the refrig-...
  • Page 11: General

    INDOOR NON-ADJUSTABLE COIL THERMAL EXPANSION VALVE FOR COOLING (10°F SUPER HEAT) BRAZED CONNECTIONS COOLING CYCLE FLOW HEATING CYCLE FLOW FIG. 6 - REFRIGERANT FLOW DIAGRAM GENERAL During the cooling cycle, when the reversing valve solenoids becomes energized, operation will be the same as any conven- tional air conditioning system.
  • Page 12: Heating Operation

    035-16192-001-A-1001 through the defrost control boards and safety switches to energize relays RY1 and RY2, which in turn will energize contactors 1M & 3M, starting the compressors. Contactors 2M and 4M are energized through the NO contacts on auxil- iary contactors 1M-AUX and 3M-AUX in order to start the outdoor fan motors.
  • Page 13: Operation Below 0°F

    OPERATION BELOW 0°F OUTDOOR TEMPERA- TURE 1. At 0°F outdoor temperature, the low temperature compres- sor cutoff thermostat TH1 and TH3 contacts 1 and 3 will open, de-energizing contactor 1M and 3M which shuts down the compressor. Contacts 1 and 2 of thermostat TH1 and TH3 are closed when contacts 1 and 3 are open.
  • Page 14: Start-Up

    035-16192-001-A-1001 CRANKCASE HEATER The crankcase heaters must be energized at least 8 hours bef- ore starting the compressor. To energize the crankcase heat- ers, the main disconnect switch must be closed. During this 8 hour period, the system switch on the room thermostat must be “OFF”...
  • Page 15: Charging Curves Efb180A

    FIG.7 - COOLING MODE CHARGING CHART - EFB180A FIG. 8 - COOLING MODE CHARGING CHART -EFB240A Unitary Products Group Suction Pressure (psig) Suction Pressure (psig) 035-16192-001-A-1001 ODDB 115 °F 105 °F 95 °F 85 °F 75 °F ODDB 115 °F 105 °F 95 °F 85 °F...
  • Page 16: Heating Mode Charging Chart At 4800 Cfm

    035-16192-001-A-1001 FIG. 9 - HEATING MODE CHARGING CHART AT 4800 CFM - EFB180A FIG. 10 - HEATING MODE CHARGING CHART AT 6000 CFM - EFB180A Suction Pressure (psig) Suction Pressure (psig) IDDB 80 °F 70 °F 60 °F IDDB 80 °F 70 °F 60 °F Unitary Products Group...
  • Page 17: Heating Mode Charging Chart At 6600 Cfm

    FIG. 11 - HEATING MODE CHARGING CHART AT 6600 CFM - EFB180A FIG. 12 - HEATING MODE CHARGING CHART AT 6400 CFM - EFB240A Unitary Products Group Suction Pressure (psig) Suction Pressure (psig) 035-16192-001-A-1001 IDDB 80 °F 70 °F 60 °F IDDB 80 °F 70 °F...
  • Page 18: Heating Mode Charging Chart At 7000 Cfm

    035-16192-001-A-1001 FIG. 13 - HEATING MODE CHARGING CHART AT 7000 CFM - EFB240A FIG. 14 - HEATING MODE CHARGING CHART AT 7600 CFM - EFB240A Suction Pressure (psig) Suction Pressure (psig) IDDB 80 °F 70 °F 60 °F IDDB 80 °F 70 °F 60 °F Unitary Products Group...
  • Page 19 035-16192-001-A-1001 NOTES Unitary Products Group...
  • Page 20 Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 035-16192-001-A-1001 Subject to change without notice. Printed in U.S.A Copyright  by York International Corporation 2001. All Rights Reserved. Supersedes: 035-16192-000 (0601) Code: SBY...

This manual is also suitable for:

E1fb240E1fb180a25E1fb180a46E1fb240a25E1fb240a46

Table of Contents