P24A & P34A Service Manual
Condensing
Temp. °F
100
100
100
100
100
100
100
100
Condensing
Temp. °F
100
100
100
100
100
100
100
100
12/18/12
Entering
Leaving
Water
Water
Temp. °F
Temp. °F
50
95
55
95
60
95
65
95
70
95
75
95
80
95
85
95
P24A Condenser Water Usage
Entering
Leaving
Water
Water
Temp. °F
Temp. °F
50
95
55
95
60
95
65
95
70
95
75
95
80
95
85
95
P34A Condenser Water Usage
Water Flow
gpm
42
47
53
62
75
93
125
187
Table 11-4
Water Flow
gpm
82
93
106
124
148
185
241
371
Table 11-5
TABLES & CHARTS
Pressure
Average Total Heat
Drop
of Rejection
psig
BTU/HR
1
981,300
1
981,300
1
981,300
2
981,300
2
981,300
3
981,300
6
981,300
14
981,300
Pressure
Average Total
Drop
Heat
psig
of Rejection
BTU/HR
1
1,852,500
1
1,852,500
1
1,852,500
1
1,852,500
2
1,852,500
3
1,852,500
5
1,852,500
12
1,852,500
11-5