1. In HW Config, select the PROFINET-capable module (CPU or CP).
2. Open the "Properties" dialog box of the PROFINET interface.
3. Select the "Manager" role on the "Media Redundancy" tab.
4. Click "OK".
5. Select the interface modules (IM) in HW Config.
6. Open the "Properties" dialog box of the IM.
7. Select the "Client" role on the "Media Redundancy" tab.
8. Click "OK".
Additional information
● Online help on
4.3.7

How to configure the redundant PROFIBUS PA

Introduction
The following is a description of how to configure a redundant PROFIBUS PA that is connected
to a redundant PROFIBUS DP.
You can find configuration variants in the section "Fault-tolerant PROFIBUS PA (Page 74)".
Requirements
● The PCS 7 project with a SIMATIC H station is open in SIMATIC Manager.
● Two DP master systems are configured for the SIMATIC H station in HW Config and these
are used as connection paths for the redundant interface.
● For commissioning: The PROFIBUS addresses are set with the DIL switches on the
FDC 157-0 DP/PA couplers.
● You can install a maximum of 5 FDC 157-0 DP/PA couplers, one coupler pair of which is
used at the end of the configuration in redundant mode.
Fault-tolerant Process Control Systems (V8.1)
Function Manual, 11/2014, A5E34878832-AA
STEP 7
Advantages of fault-tolerant components
4.3 Communication connections
123