Cooling Capacities For Dj240 - York DJ 210 Technical Manual

Single package gas/electric units and single package air conditioners
Hide thumbs Also See for DJ 210:
Table of Contents

Advertisement

261660-YTG-D-0708
TABLE 6: COOLING CAPACITIES FOR DJ240
Air on Evaporator Coil
Total
WB
CFM
Cap.
(°F)
(MBH)
72
273.1 16.90 149.8 132.7 115.6 98.5 81.4
67
248.6 16.43 197.6 180.5 163.4 146.3 129.1 112.0 94.9
6000
62
231.2 16.44 227.9 210.8 193.7 176.6 159.5 142.4 125.3 215.2 17.64 215.2 200.8 183.7 166.6 149.5 132.4 115.3
57
216.6 15.98 216.6 210.2 193.1 176.0 158.9 141.8 124.7 221.2 17.98 221.2 213.2 196.1 179.0 161.8 144.7 127.6
72
278.7 16.96 165.8 145.6 125.4 105.1 84.9
67
253.8 16.49 217.5 197.3 177.1 156.9 136.7 116.5 96.2
7000
62
236.0 16.50 234.4 225.8 210.0 189.8 169.6 149.4 129.2 221.5 17.70 221.5 214.3 200.7 180.5 160.3 140.0 119.8
57
221.1 16.04 221.1 217.9 209.3 189.1 168.9 148.7 128.5 227.6 18.04 227.6 223.6 214.2 194.0 173.8 153.5 133.3
72
284.4 17.02 181.8 158.4 135.1 111.8 88.4
67
259.0 16.55 237.5 214.2 190.9 167.5 144.2 120.9 97.6
8000
62
240.8 16.56 240.8 240.8 226.3 203.0 179.7 156.4 133.0 227.7 17.76 227.7 227.7 217.7 194.4 171.0 147.7 124.4
57
225.6 16.10 225.6 225.6 225.6 202.3 178.9 155.6 132.3 234.0 18.10 234.0 234.0 232.3 209.0 185.7 162.4 139.0
72
291.0 17.43 193.1 167.5 141.8 116.1 90.4
67
265.0 16.95 251.7 226.0 200.3 174.7 149.0 123.3 97.6
8700
62
246.4 16.96 246.4 246.4 237.6 211.9 186.2 160.5 134.9 232.2 18.14 232.2 232.2 227.2 201.5 175.8 150.1 124.5
57
230.8 16.49 230.8 230.8 230.8 205.2 179.5 153.8 128.1 238.6 18.50 238.6 238.6 237.7 212.1 186.4 160.7 135.0
72
297.7 17.84 204.5 176.5 148.5 120.5 92.4
67
271.0 17.35 265.8 237.8 209.8 181.8 153.7 125.7 97.7
9400
62
252.0 17.36 252.0 252.0 248.8 220.7 192.7 164.7 136.7 236.6 18.53 236.6 236.6 236.6 208.6 180.6 152.6 124.6
57
236.1 16.88 236.1 236.1 236.1 208.1 180.1 152.0 124.0 243.2 18.89 243.2 243.2 243.2 215.1 187.1 159.1 131.1
72
244.1 20.09 146.5 129.4 112.3 95.2 78.1
67
225.3 19.63 186.7 169.6 152.5 135.4 118.3 101.2 84.1
6000
62
202.7 19.37 202.7 194.9 177.7 160.6 143.5 126.4 109.3 190.2 21.09 190.2 188.9 171.8 154.7 137.6 120.5 103.4
57
211.7 19.63 211.7 205.7 188.6 171.5 154.4 137.3 120.2 202.2 21.28 202.2 198.2 181.1 164.0 146.9 129.8 112.7
72
250.6 20.15 162.5 142.2 122.0 101.8 81.6
67
231.3 19.69 206.2 185.9 165.7 145.5 125.3 105.1 84.9
7000
62
208.1 19.43 208.1 204.2 193.1 172.9 152.7 132.5 112.3 194.8 21.16 194.8 194.1 185.6 165.4 145.1 124.9 104.7
57
217.3 19.70 217.3 214.3 204.9 184.7 164.5 144.3 124.1 207.0 21.35 207.0 205.1 195.7 175.4 155.2 135.0 114.8
72
257.0 20.22 178.4 155.1 131.7 108.4 85.1
67
237.3 19.76 225.6 202.3 178.9 155.6 132.3 109.0 85.6
8000
62
213.5 19.50 213.5 213.5 208.5 185.2 161.9 138.5 115.2 199.4 21.24 199.4 199.4 199.4 176.0 152.7 129.4 106.1
57
222.9 19.77 222.9 222.9 221.3 197.9 174.6 151.3 128.0 211.9 21.43 211.9 211.9 210.2 186.9 163.5 140.2 116.9
72
264.1 20.56 191.3 165.6 139.9 114.3 88.6
67
243.8 20.09 238.0 215.7 190.0 164.4 138.7 113.0 87.3
8700
62
219.4 19.83 219.4 219.4 216.9 191.2 165.5 139.8 114.2 206.6 21.51 206.6 206.6 206.6 180.9 155.2 129.5 103.9
57
229.0 20.10 229.0 229.0 228.2 202.5 176.9 151.2 125.5 219.5 21.70 219.5 219.5 218.7 193.0 167.3 141.7 116.0
72
271.1 20.91 204.1 176.1 148.1 120.1 92.1
67
250.3 20.43 250.3 229.2 201.1 173.1 145.1 117.1 89.1
9400
62
225.2 20.16 225.2 225.2 225.2 197.2 169.2 141.1 113.1 213.8 21.78 213.8 213.8 213.8 185.7 157.7 129.7 101.7
57
235.2 20.43 235.2 235.2 235.2 207.1 179.1 151.1 123.1 227.2 21.98 227.2 227.2 227.2 199.2 171.1 143.1 115.1
72
217.6 23.35 139.1 122.0 104.9 87.8 70.7
67
201.4 23.23 175.7 158.6 141.5 124.4 107.3 90.2 73.1
6000
62
177.7 22.82 177.7 177.7 165.8 148.7 131.6 114.5 97.4
57
192.7 22.93 192.7 190.8 173.7 156.5 139.4 122.3 105.2
72
222.2 23.43 153.1 132.8 112.6 92.4 72.2
67
205.6 23.31 192.3 172.1 151.9 131.7 111.4 91.2 71.0
7000
62
181.5 22.90 181.5 181.5 178.0 157.8 137.6 117.4 97.1
57
196.8 23.01 196.8 195.8 186.4 166.2 146.0 125.7 105.5
72
226.8 23.51 167.0 143.7 120.3 97.0 73.7
67
209.9 23.39 208.9 185.6 162.3 138.9 115.6 92.3 68.9
8000
62
185.2 22.98 185.2 185.2 185.2 166.9 143.5 120.2 96.9
57
200.8 23.09 200.8 200.8 199.1 175.8 152.5 129.1 105.8
72
237.2 23.74 182.7 157.0 131.3 105.7 80.0
67
219.5 23.61 219.0 202.8 177.1 151.5 125.8 100.1 74.4
8700
62
193.7 23.19 193.7 193.7 193.7 170.6 144.9 119.2 93.6
57
210.0 23.30 210.0 210.0 209.2 183.5 157.8 132.1 106.5
72
247.6 23.96 198.4 170.4 142.4 114.3 86.3
67
229.1 23.84 229.1 220.0 192.0 164.0 136.0 107.9 79.9
9400
62
202.3 23.41 202.3 202.3 202.3 174.3 146.3 118.2 90.2
57
219.2 23.52 219.2 219.2 219.2 191.2 163.2 135.1 107.1
1.
The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
12
85°F
2
Total
Sensible Capacity (MBH)
1
Input
Return Dry Bulb (°F)
(kW)
86
83
80
105°F
125°F
Temperature of Air on Condenser Coil
*
Total
1
Cap.
77
74
71
68
(MBH)
-
-
257.3 18.45 150.2 133.1 116.0 98.9 81.8
237.3 17.83 192.3 175.1 158.0 140.9 123.8 106.7 89.6
-
-
264.7 18.51 167.2 146.9 126.7 106.5 86.3
244.2 17.89 213.1 192.9 172.7 152.4 132.2 112.0 91.8
-
-
272.2 18.58 184.1 160.8 137.4 114.1 90.8
251.0 17.95 233.9 210.6 187.3 164.0 140.6 117.3 94.0
-
-
277.5 18.98 195.6 169.9 144.2 118.5 92.9
256.0 18.33 247.4 222.2 196.5 170.8 145.2 119.5 93.8
-
-
282.9 19.38 207.0 179.0 151.0 123.0 94.9
260.9 18.72 260.9 233.7 205.7 177.7 149.7 121.7 93.6
-
-
230.8 21.72 142.8 125.7 108.6 91.5 74.4
213.4 21.43 181.2 164.1 147.0 129.9 112.8 95.7 78.6
-
-
236.4 21.79 157.8 137.5 117.3 97.1 76.9
218.5 21.50 199.2 179.0 158.8 138.6 118.4 98.1 77.9
-
-
241.9 21.87 172.7 149.4 126.0 102.7 79.4
223.6 21.58 217.3 193.9 170.6 147.3 123.9 100.6 77.3
-
-
250.6 22.15 187.0 161.3 135.6 110.0 84.3
231.7 21.85 228.5 209.3 183.6 157.9 132.2 106.6 80.9
-
-
259.4 22.43 201.3 173.3 145.2 117.2 89.2
239.7 22.13 239.7 224.6 196.6 168.6 140.5 112.5 84.5
-
-
-
-
-
-
-
-
-
-
95°F
2
Total
Sensible Capacity (MBH)
Input
Return Dry Bulb (°F)
(kW)
86
83
80
77
115°F
Johnson Controls Unitary Products
*
74
71
68
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-