Electrical Data - Df072 Belt Drive W/Powered Conv. Outlet; Electrical Data - Df072 Direct Drive W/Powered Conv. Outlet - York DF 072 Technical Manual

Single package gas/electric units and single package air conditioners
Table of Contents

Advertisement

254599-YTG-C-0807
TABLE 13: ELECTRICAL DATA - DF072 BELT DRIVE W/POWERED CONV. OUTLET
COMPRESSORS
MODEL
VOLTAGE
RLA
TONNAGE
EACH
208-3-60
20.7
230-3-60
20.7
DF072
(6.0)
460-3-60
10.0
575-3-60
8.2
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 14: ELECTRICAL DATA - DF072 DIRECT DRIVE W/POWERED CONV. OUTLET
COMPRESSORS
MODEL
VOLTAGE
RLA
TONNAGE
EACH
208-3-60
20.7
DF072
(6.0)
230-3-60
20.7
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
ID
OD FAN
BLOWER
MOTOR
LRA
MOTOR
FLA
EACH
FLA
156.0
2.3
5.2
156.0
2.3
5.2
75.0
1.3
2.6
54.0
1.3
2.0
ID
OD FAN
BLOWER
MOTOR
LRA
MOTOR
FLA
EACH
FLA
156.0
2.3
10.6
156.0
2.3
10.6
CONV
ELECTRIC HEATER
OUTLET
MODEL NO.
FLA
None
2
2CE04510525
2
2CE04510725
10.0
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2
2CE04510525
2
2CE04510725
10.0
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2
2CE04510746
2
2CE04511046
5.0
2
2CE04511546
2
2CE04512046
2
2CE04513046
None
2CE04511058
4.0
2CE04511558
2CE04512058
2CE04513058
CONV
ELECTRIC HEATER
OUTLET
MODEL NO.
FLA
None
2
2CE04510525
2
2CE04510725
10.0
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2
2CE04510525
2
2CE04510725
10.0
2CE04511025
2CE04511525
2CE04512025
2CE04513025
MIN.
HEATER
HEATER
CIRCUIT
KW
AMPS
AMPACITY
(AMPS)
-
-
43.4
4
11.1
43.4
5.6
15.5
43.4
8
22.2
46.8
11.9
33.0
60.3
15.9
44.1
74.2
22.2
61.6
96
-
-
43.4
5.3
12.7
43.4
7.5
18.0
43.4
10.6
25.5
50.9
15.9
38.2
66.8
21.2
51.0
82.7
29.6
71.2
108
-
-
21.4
6.8
8.2
21.4
10.1
12.1
24.7
13.6
16.4
29.9
19.5
23.5
38.8
28.8
34.6
52.8
-
-
17.3
10.6
10.2
20.2
15.9
15.3
26.6
21.2
20.4
33
30.4
29.3
44.1
MIN.
HEATER
HEATER
CIRCUIT
KW
AMPS
AMPACITY
(AMPS)
-
-
48.8
4.0
11.1
48.8
5.6
15.5
48.8
8.0
22.2
53.5
11.9
33.0
67.0
15.9
44.1
80.9
22.2
61.6
102.8
-
-
48.8
5.3
12.7
48.8
7.5
18.0
48.8
10.6
25.5
57.6
15.9
38.2
73.6
21.2
51.0
89.5
29.6
71.2
114.8
MAX. FUSE/
1
BRKR
SIZE
(AMPS)
60
60
60
60
70
80
100
60
60
60
60
70
90
110
30
30
30
30
40
60
25
25
30
35
45
MAX. FUSE/
1
BRKR
SIZE
(AMPS)
60
60
60
60
70
90
110
60
60
60
60
80
90
125
13