Troubleshooting - EcoSmart G37T Installation, Operation And Maintenance Manual

Gas burner
Table of Contents

Advertisement

ENGLISH
Troubleshooting - General
Symptom
Appliance won't
1.
light
Low flames or
2.
won't stay lit
3.
Blue Flames
4.
Metallic noise
Ignitor makes
clicking sound
5.
but no visible
spark is produced
Possible Causes
A.
No LP in tank, or NG main not turned on.
B.
Plugged burner orifice.
C.
No spark igniting burner.
D.
Excessive media build up around igniter.
Manual shutoff valve (on/off control knob) open or not
A.
in- stalled between LP tank and appliance.
Improper air shutter adjustment.
B.
Improper gas supply pressure.
C.
Burner was not converted for natural gas.
D.
Thermocouple not properly secured to valve.
E.
This is a result of normal operation and flames will
begin to yellow as unit is allowed to burn for 15-20
A.
minutes.
Improper air/fuel mixture related to air shutter
B.
position.
Burner was not converted for natural gas.
C.
Noise is caused by metal expanding and contracting
as it heats up and cools down, similar to the sound
A.
produced by a furnace or heating duct. This noise does
not affect the operation or longevity of the appliance.
Ignitor is improperly grounded.
A.
Ignition or ground wire not plugged in.
B.
Ignition electrode set too far from grounding probe.
C.
Excessive media build up around igniter.
D.
Corrective Actions
Check the LP (propane) tank. You may be out of
gas. Or check Natural Gas valve at main.
Check the burner orifice for stoppage.
Remove stoppage.
Refer to ignitor in section 6.
Ensure that media installation instructions are
followed, and media or debris is not present inside
the ignition wind guard.
Close LP tank and manual shutoff valves. Open LP tank
valve first, THEN follow instructions for lighting up.
The air shutter is adjusted from the factory for
optimal performance. For NG, air shutter should be
closed. For LP, air shutter should be ¼" open.
Ensure that the appliance is operating at the ideal
inlet gas pressure detailed on Page 1. This should
be done by a licensed plumber.
Both valve orifice and burner orifice must be
changed, and the air shutter must be closed. Follow
conversion instructions on Page 14.
Ensure the thermocouple is tightened to control
valve using 10mm wrench.
No action required.
The air shutter is adjusted from the factory for
optimal performance. For NG, air shutter should be
closed. For LP, air shutter should be ¼" open.
Both valve orifice and burner orifice must be
changed, and the air shutter must be closed. Follow
conversion instructions on Page 14.
No action required.
Check all wire connections at back of sparker box.
Ensure ignitor wire and grounding wire are securely
attached to burner.
Check that ignition electrode and ignition wind
guard wall is within 1/8" to 3/16".
Ensure that the media installation instructions are
followed, and media is not present inside the ignition
wind guard.