Start-Up; Procedure - Helios ETR Installation And Operating Specification

Electronic temperature controller
Table of Contents

Advertisement

Available languages

Available languages

Installation and Operating Specification ETR
Minimum speed cut off
Uout
[V]
10
Msco. = OFF
5
H

8 Start-up

8.1 Procedure

1. You must mount and connect the device in accordance with
the operating instructions.
2. Double check that all connections are correct.
3. The supply voltage must match the information on the rating
plate.
4. Set the operating Mode in the BASE SETUP (factory settings
2.01
5. When saving the Operating Mode, the factory settings are
stored.
Therefore the settings you have made, e.g. in "SETTING" are
lost.
L-BAL-E193-GB 1320
Min. Uout = 3.5 V
Max. Uout = 10.0 V
Msco. = -2.0 K
7 K
20 °C
Pband
Setpoint
).
Attention, electrostatic sensitive devices!
Be sure to ground the board at a suitable point in order to prevent
damage to the electronic components being caused by electro-
static discharges. Such damage could occur, e.g., if a metal
water pipe or heating line are briefly touched.
Actual Value
[°C]
27 °C
06.05.2010
v_min_luft_abschalt_ctg.vsd
Part.-No.
16/20
Start-up