4.3 Temperature influences during commissioning
Avoid condensation in the controller and functional faults attribut-
able to condensation by storing the controller at room temper-
ature!

5 Electrical installation

5.1 Safety precautions

Danger due to electric current
Work on electric components may only be carried out by
trained electricians or by persons instructed in electricity
under the supervision of an electrician in accordance with
electrical engineering regulations.
The programming of the equipment takes place with switched
on supply voltage by opened cover and voltage for change-
over Setpoint 1/2. Use power supplies which guarantee reli-
able electrical isolation of the operating voltage as per IEC/-
DIN EN 60204-1. Consider also the general requirements for
PELV circuits in accordance with IEC/DIN EN 60204-1.
Inspect electrical equipment periodically: retighten loose con-
nections – immediately replace damaged lines and cables.
Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of
this manual (

5.2 EMC-compatible installation of control lines

Pay attention to maintain sufficient distance from powerlines and
motor wires to prevent interferences. The control cable may not be
longer than 30 m. Screened control cables must be used when the
cable length is longer than 20 m!
L-BAL-E193-GB 1320
Connection diagram)!
Part.-No.
8/20
Electrical installation