Important informations
- Work on the mains may only be carried out by specialists.
-The installation must be carried out in accordance with the national standards.
- Disconnect the 230 volt power supply each time before starting to install!
-The detector is always supplied with a fuse (250VAC, 10A)
Type C, to be provided as a protective measure in accordance with EN60898-1.
-The device must not be installed on conductive surfaces.
-The detector is only suitable for indoor use
-To ensure the functioning of the detector bulbs installed at the same height are a
minimum distance
-Lights which are below the detector and in the detection area
positioned can lead to malfunctions (light never torn off, or on/off .
-Should malfunctions such as steady light, independent on and
turn off occur, see page 7 '' Troubleshooting ''.
Function
The detector reacts to heat misplacement (positive or negative in relation to the
environment). If a person approaches the monitored area, the connected lamp is
automatically switched on.
If it leaves the area, it is switched off again after an adjustable time of 10 seconds
to 20 minutes.
The connected light is only switched on when the natural brightness falls below
the value set on the device, the artificial light is regulated and thus the mixed light
lighting is kept constant.
The artificial light is automatically switched off again as soon as the natural
brightness value is exceeded. This activates the additional power saving function
when there is enough natural light.
Installation
Phase / outer conductor (L); Neutral / neutral (N);
Switching output DALI 2-pole broadcast, constant light control (DA / DA)
Optional terminals:
S: Connection of slave detectors (max. 10 pieces)
R: by means of (supplying the phase) pulse button (use without glow lamp!), Or
by means of a potential-free button between T1 / T2, the light can be switched on
or off and dimmed. Keep the cable short!
Screw the device into the inlet socket. The detector is ready for use approx. 1
minute after connection to the mains. Then set the controls or use the handheld
transmitter.
Mechanical changes in controller values are only accepted by the detector during
operation. Then put the lens on (lens must be installed otherwise the device will
not switch off).
2