Amana CVC96 BB Series Installation Instructions Manual page 31

Two-stage gas furnace
Hide thumbs Also See for CVC96 BB Series:
Table of Contents

Advertisement

1. Measure resistance between the neutral (white)
connection and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock
switch which interrupts unit voltage when the blower door
is opened for servicing. Do not defeat this switch.
CoolCloud™ HVAC Phone Application
Actual screens may look different based on the mobile
device being used.
Figure 46
Figure 47
This furnace is Bluetooth ready and functions with the
CoolCloud HVAC phone application designed to improve
the contractor's setup / diagnostic experience. Users can
see specific model information, review active diagnostic
error codes, observe system status during operation,
make system menu adjustments, add site visit notes and
run system testing of all operational modes (heat / cool /
fan) directly from the phone. The phone application is also
capable of directly updating the furnace software anytime
updates are available. The application will automatically
notify the user if updates are available.
NOTE: The software update may take up to 20
minutes to complete.
Quick Start Guide For Communicating Outdoor
Units
EXTREMELY IMPORTANT: For all cooling calls the system
only requires a single Y input from the thermostat. For all
heating calls (including dual fuel applications) the system
only requires a single W input from the thermostat. Internal
algorithms will control all available cooling and heating
stages including dual fuel operation based on these inputs.
Any single-stage 24VAC thermostat can be used. For
proper operation the thermostat must be setup to control a
single-stage AC outdoor unit and to control a single stage
gas furnace. The control board does not accommodate an
O wire thermostat input (reversing valve signal). If a heat
pump is installed, the thermostat should be setup as stated
above. Setting the thermostat for the heat pump control or
multi stage control may result in incorrect performance.
1. Connect all necessary thermostat wires to the
thermostat connector on the furnace control as
31
Figure 48