Amana CVC96 BB Series Installation Instructions Manual page 25

Two-stage gas furnace
Hide thumbs Also See for CVC96 BB Series:
Table of Contents

Advertisement

aluminum-alloy tubing and connectors are coated to
protect against external corrosion when in contact
with masonry, plaster, or insulation, or subjected to
repeated wetting by liquids such as water (except rain
water), detergents, or sewage.
The gas piping may enter the left or right side of the
furnace cabinet. The installer must supply rigid pipe long
enough to reach the outside of the cabinet to seal the
grommet cabinet penetration. A semi-rigid connector to the
gas piping can be used outside the cabinet per local codes.
1/2" NPT pipe and fittings are required. For models with an
"L" shaped manifold, a 4 1/2" long nipple is required. For
models with a hook shaped manifold, a 2" long nipple is
required.
A semi-rigid connector to the gas piping can be used
outside the cabinet per local codes. From the elbow, the
length of pipe and the fittings required will vary by the side
chosen, location of union and cabinet width. The union may
be placed inside or outside of the cabinet.
Alternate
Manifold
Gas Line
Location
Gas Valve
*Ground
Joint
Pipe
Union
*NOTE: Union may be inside furnace cabinet where allowed by local codes.
Manual Shut Off Valve
(upstream from ground joint pipe union)
*Ground
Joint
Pipe Union
Grommet
in Standard
Gas Line
Hole
Drip Leg
*NOTE: Union may be inside furnace cabinet where allowed by local codes.
Manual Shut Off Valve
Burners
(upstream from
ground joint
pipe union)
*Ground
Joint
Pipe
Union
Drip Leg
Grommet
in Standard
Gas Line
Hole
Figure 32
Plug in
Alternate
Gas Line
Hole
Gas Valve
Burners
Figure 33
Standard Gas Line Hole
Burners
Alternate
Gas Line
Location
*Ground
Joint
Gas Piping Checks
Pipe Union
To avoid the possibility of explosion or fire,
never use a match or open flame to test for
leaks.
Before placing unit in operation, leak test the unit and gas
connections.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved testing methods.
25
Manual Shut Off Valve
Alternate
Union
Location
Drip Leg
Grommet in
Plug in Alternate Gas Line Hole
Plug in Main Gas Line Hole
Gas
Manifold
Valve
Drain Trap
Figure 34
Figure 35
CAUTION
(upstream from
ground joint pipe union)
Manual Shut Off Valve
(upstream from
ground joint
pipe union)