Appendix
Message
Open/Close (on/off)
96
Possible reasons
− The breakaway time or
transit time differs from the
reference value by the
amount entered in 'Limit
value time analysis'.
− The valve end position dif-
fers from the reference
value by the amount en-
tered in 'Limit value travel
analysis'.
− The end position cannot
be reached.
Recommended action
− Check that pneumatic
installations and con-
nections are tight.
− Check supply pressure.
− Check plug stem for ex-
ternal influences that
could be blocking it.
Status clas-
sification
Single reset
•
•
[
]
Sec. 3.1.3
u