Note:
The 'Measured data storage out
of memory' reading (Maintenance
alarm) is generated when the 'Scan
rate' is too low. After recording 100
measured values per variable, log-
ging is stopped, but the test continues
until it is completed.
After the full stroke test is canceled, the 'Sta-
tus of full stroke test' reading indicates 'Not
successful'. The reason for cancelation is
marked by the 'Maintenance alarm' mes-
sage in the Analysis of measured data fold-
er (> Current test).
Defining parameters
1. Switch to manual mode.
2. Define parameters for full stroke test. See
u Note concerning setting the FST diag-
nostic parameters on page 77.
3. Configure the cancelation conditions.
4. Select classification for status message.
5. Start full stroke test.
The 'Test information' status indicates
'Test active'. 'd6' and 'tEST' are indicated
in alternating sequence on the positioner
display. 'Function check'
as the condensed state.
Operation > Operating mode
1.
− Target mode (Code 0): Manual
Diagnosis > Tests > Full stroke test
2.
− Tolerance limit of step response:
0.1 to 10.0 %, [2.0 %]
− Activation of the ramp function: [Yes], No
EB 8389S EN
3. − Max. test duration:
4.
5.
is activated
Note concerning setting the FST diagnostic
parameters
− The 'Ramp time (rising)' must be greater
− The 'Ramp time (falling)' must be greater
− Settling time before test start:
1 to 240 s, [10 s]
− Delay time after step:
2.0 to 100.0 s, [2.0 s]
− Scan rate: 0.2 to 250.0 s, [1.4 s]
Only when the ramp function is activated:
− Ramp time (rising): 0 to 9999 s, [60 s]
− Ramp time (falling): 0 to 9999 s, [60 s]
30 to 25000 s, [150 s]
Settings > Positioner > Error control >
Classification report > Extended > PST/FST
− PST/FST - Status active:
, [
],
,
Diagnosis > Tests > Full stroke test
− Start test
Note:
Cancel the test by right-clicking 'Stop
test' and selecting 'Execute' or by
pressing the rotary pushbutton at the
positioner. After the test has been
canceled, the positioner remains in
manual mode.
than the corresponding value for 'Mini-
mum transit time close' (Code 41) deter-
mined during initialization.
than the corresponding value for 'Mini-
Tests
77