Code
Parameter – Readings/
no.
values [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
49* h
Application type (valve)
h0 Application type
[No], YES, ESC
h1 Operating point
0.0 to [100.0 %] of the
valve position
h2 Limit fail-safe position
0.0 to 20.0 % of the
reference variable,
[12.5 %]
h3 Lower limit to start test
[25.0 % of reference
variable]
h4 Upper limit to start test
[50.0 % of reference
variable]
h5 Operating point limit
55.0 to 100.0 % of
reference variable,
[75.0 %]
h6 Unassigned
h7 Travel time assessment
limit
[0.6] to 30.0 s
h8 Travel assessment limit
0.1 to 100.0 % of the
valve position, [0.3 %]
EB 8389S EN
Description
No
Control valve
YES
Open/close (on/off) valve
Depending on the adjusted application type, the positioner responds
differently in automatic mode and there are differences in the diag-
nostic functions.
The valve is moved to this valve position as soon as the reference
variable exceeds the limit operating point (Code 49 – h5).
The valve is moved to its fail-safe position (SAFE) when the value
falls below this limit.
The valve remains in its last valid position between the fail-safe posi-
tion limit and the lower test limit. A partial stroke test is performed
after six seconds when the valve is between the upper and lower test
limit.
Read only
The valve remains in its last valid position between the upper test lim-
it and the operating point limit.
Read only
Valve is moved to the operating point when the operating point limit
is exceeded.
Time limit for difference between reference value and currently re-
corded value. Determines the difference at which a message is gen-
erated.
Travel limit for difference between reference value and currently re-
corded value. Determines the difference at which a message is gen-
erated.
Appendix