Samson TROVIS SAFE 3731 Series Operating Instructions Manual page 28

Electropneumatic positioner
Hide thumbs Also See for TROVIS SAFE 3731 Series:
Table of Contents

Advertisement

Statistical information
limit ('Trigger value' – ½ 'Trigger band') or
falls below the upper limit ('Trigger value' +
½ 'Trigger band').
This function is only active when 'Trigger
band' ≠ 0.
Note:
The bottom band limit assumes the
value 0.0 % or 0.0
The top band limit assumes the value
100.0 % or 100.0
Diagnosis > Statistical information > Data
logger
− Selection: Trigger
1.
2. − Trigger status: Start trigger via set point,
valve position, drive signal or set point devi-
ation
− Trigger value:
0.0 to 100.0 %, [99.0 %] (set point, valve
position, set point deviation)
0.0 to 10000.0
− Trigger band:
0.0 to 100.0 %, [99.0 %] (set point, valve
position, set point deviation)
0.0 to 10000.0 1/s, [99.0 1/s] (drive sig-
nal)
− Pre-trigger time:
0.0 s to 100 x 'Scan rate', [0.0 s]
− Trigger edge: [Low signal/falling edge/bot-
tom band exit], High signal/rising edge/top
band exit, Band exit, Band entry
3. − Scan rate: 0.2 to 3600.0 s, [1.0 s]
4. − Start data logger
28
at the lowest.
1
/
s
at the most.
1
/
s
, [99.0
] (drive signal)
1
/
1
/
s
s
3.2.2.3 Triggered by internal sole-
noid valve/forced venting
Triggering by the internal solenoid valve/
forced venting is only active when an inter-
nal solenoid valve/forced venting is installed
in the positioner. See 'Internal solenoid
valve/forced venting' reading (Code 45).
The measured values are included in the trig-
gered data logging when the solenoid valve
is triggered or the forced venting is activat-
ed.
Diagnosis > Data logger
− Selection: Trigger
1.
2. − Trigger status:
Start trigger via int. sol. valve/forced vent-
ing
− Pre-trigger time:
0.0 s to 100 x 'Scan rate', [0.0 s]
3. − Scan rate: 0.2 to 3600.0 s, [1.0 s]
4. − Start data logger
3.2.2.4 Triggered by set point or
internal solenoid valve/
forced venting
Triggering by the internal solenoid valve/
forced venting is only active when an inter-
nal solenoid valve/forced venting is installed
in the positioner. See 'Internal solenoid
valve/forced venting' reading (Code 45).
The measured values are included in the trig-
gered data logging when one of the condi-
tions defined in 'Start trigger via internal so-
EB 8389S EN