Samson TROVIS SAFE 3731 Series Operating Instructions Manual page 29

Electropneumatic positioner
Hide thumbs Also See for TROVIS SAFE 3731 Series:
Table of Contents

Advertisement

lenoid valve/forced venting' or 'Start trigger
via set point' are met.
Diagnosis > Data logger
1.
− Selection: Trigger
2. − Trigger status:
Start trigger via set point/int. sol. valve/
forced venting
− Trigger value:
0.0 to 100.0 %, [99.0 %]
− Trigger band: 0.0 to 100.0 %, [99.0 %]
− Pre-trigger time:
0.0 s to 100 x 'Scan rate', [0.0 s]
− Trigger edge: [Low signal/falling edge/bot-
tom band exit], High signal/rising edge/top
band exit, Band exit, Band entry
3. − Scan rate: 0.2 to 3600.0 s, [1.0 s]
4. − Start data logger
3.2.2.5 Triggered by binary input
Positioners can be optionally fitted with a bi-
nary input. Triggering by the binary input is
only active when the positioner is fitted with
a binary input.
The measured values are included in the trig-
gered data logging when the state of the bi-
nary input changes.
Diagnosis > Statistical information > Data
logger
1.
− Selection: Trigger
2. − Trigger status:
Start trigger via binary input
− Pre-trigger time:
0.0 s to 100 x 'Scan rate', [0.0 s]
3. − Scan rate: 0.2 to 3600.0 s, [1.0 s]
EB 8389S EN
4. − Start data logger
Statistical information
29