Installation Instructions
October 9, 2019
Applications Requiring a Secure Enclosure
For any application requiring a secure enclosure, mount
the PXC Compact inside a listed enclosure along with a
Service Box and Sidewall Kit, if needed.
Power Requirements
One of the following power sources is pulled to the
enclosure:
120 Vac, 60 Hz and terminated at the 115V PX
Series Service Box.
230 Vac, 50/60 Hz and terminated at the 230V
PX Series Service Box.
24 Vac, 50/60 Hz Class 1 power limited from a
third-party transformer and connected to a
terminal block.
If powering a TX-I/O expansion panel, power
wiring is run from the transformer in the primary
panel to the expansion panel, if needed.
CAUTION:
For information on extending the TX-I/O island
bus outside the enclosure, see the APOGEE
Wiring Guidelines for Field Panels and
Equipment Controllers (125-3002).
Depending on the module types and point
configurations used, one service box
transformer may have insufficient power for
more than two TX-I/O Power Supplies. More
power may be required if using a Modular
Series with the maximum number of TX-I/O
modules.
Page 2 of 5
Figure 1: Example ALN Configuration for Smoke Control.
Compact Series Smoke Control
Application Requirements
The modem, serial cable, and surge suppressor must be
installed inside the 19-inch or 34-inch PX Series
enclosure with a Service Box.
For modems used with smoke control applications:
The UL864 Listed surge protector is required.
Devices connected between the USB port and
the UL Listed surge protector must be located
within the same room.
A USB-to-RS-232 adaptor may be needed for UL
Listed modems or UL Listed printers that are not
configured for USB communication.
The modem may be located inside the PX Series
enclosure.
Example ALN Configuration for
Smoke Control Applications
The RS-485 ALN does not have the same restrictions as
the Ethernet ALN for smoke control. Namely, Ethernet
requires UL listed switches and routers.
The following figure displays a possible ALN
configuration for smoke control.