OPERATIONAL CHECKS

Note: This equipment must be checked regularly in compliance with local regulation and
codes of practice. For your own safety, testing should occur during the day.
The LED's can be tested by pressing the TEST button on the bottom of the case.
After installation, you should allow 24 hours for the battery pack to charge fully
before testing.
Isolate the power supply and check that the lamp remains illuminated for at least
three hours. Restore the power supply.
Each day: Check that the green charging LED is lit.
Each month (short test): Isolate the power supply and check that the lamp remains
illuminated. Record the results on the test record sheet included with these
instructions.
Every six months: Isolate the power supply and check that the lamp remains
illuminated after 1 hour. Record the results on the included test record.
Once each year: Isolate the power supply and check that the lamp is still illuminated
after 3 hours. Record the results on the included test record.
Please keep these test records in a safe place. A fire officer or other authorised
person may want to see your record of inspection and testing.

CLEANING AND MAINTENANCE

Clean the product with a soft, dry cloth only. Do not use any solvents or abrasive
chemical cleaners.
The LED lamps in this product are non-replaceable.
Changing the battery
If after a routine operation check, the lamp does not remain lit for the 3 hour period,
a new battery pack may be required. Change the battery pack as follows:
1.
Isolate from the mains supply.
2.
Remove the front panel.
3.
Unplug the battery pack connector from the PCB.
4.
Remove the old battery pack.
5.
Write the current date on the new battery pack.
6.
Secure the new battery pack in position and connect the wiring terminal connector.
7.
Refit the cover. Make sure that the screws are securely fastened.
8.
Restore mains power and allow to charge for 24 hours.
9.
Perform the full operation check and update the test record.
143mm
143mm
227mm
227mm
305mm
LED
Indicators
Test
button
Battery
Connector
Fig 2. Internal Layout
7
Lamp Connector
Circuit Board
Mains
Power
Connector
Battery
Fuse