Temperature Controller Loop Configuration Memory Map, 1 Loop - FACTS Engineering Direct Logic 405 Manual

Four loop
Table of Contents

Advertisement

TEMPERATURE CONTROLLER LOOP CONFIGURATION MEMORY MAP, 1 LOOP

Decimal Offset
Example V-Mem.
0-1 Read continually
0
1
2
3-5, Written after each temperature acquisition
3
4
5
6-8, Read if Mode Word bit 0 is set (Written by Controller after Auto Tune completion)
6
7
8
9-23, Read if Mode Word bit 0 is set
9
10
11
12
13
14
15
16
17
18
19-23
V5023-V5027
2.12
Description
V5000
Mode Word
V5001
Temperature Setpoint
V5002
Output Bias
V5003
Output
V5004
Alarm Word
V5005
Process Temperature
V5006
Gain (Proportional)
V5007
Reset (Integral)
V5010
Rate (Derivative)
V5011
Low Alarm
V5012
High Alarm
V5013
Deviation Alarm
V5014
Alarm Deadband
V5015
Setpoint Low Limit
V5016
Setpoint High Limit
V5017
Input Type
V5020
PID Control Period
V5021
ON/OFF Hysteresis
V5022
Temperature Calibration
Adjustment
Reserved for Future Feature Enhancements
INSTALLATION AND WIRING
Units
bit mapped
± 3276.7 EC/EF
0.0-100.0% or 0-4095
0.0-100.0% or 0-4095
bit mapped
± 3276.7 EC/EF
0.0-6553.5
0-65535 seconds
0-65535 seconds
± 3276.7 EC/EF
± 3276.7 EC/EF
0- 3276.7 EC/EF
0.1-50.0 EC/EF
± 3276.7 EC/EF
± 3276.7 EC/EF
(0=J, 1=E, 2=K, 3=R, 4=S, 5=T)
(6=B, 7=N, 20=C)
(26=0-5V, 27=±5V)
(29=0-156.25mV,
30=±156.25mV)
(8=European Pt100,
9=American)
(10=European Pt1000)
(11=CU-10S, 12=CU-25S)
0.5-99.9 seconds
0.1-3276.7 EC/EF
± 3276.7 EC/EF