Terminal Number
G
Flame Sensor Ground
Earth G
Earth Ground
L2(N)
Line Voltage Common
3
Line Voltage Supply (L1)
4
Alarm
5
Unused
6
Burner Controller and Limits 120 Vac, 8A run, 43A inrush.
7
Unused
8
Pilot Valve/Ignition.
9
Main Fuel Valve.
10
Ignition
F(11)
Flame Sensor
12 to 21
Unused.
22
Shutter
a
The RM/EC7890 must have an earth ground providing a connection between the subbase and the control panel or the
equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in event
of an internal short circuit. The RM/EC7890 needs a low impedance ground connection to the equipment frame which,
in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF frequencies,
the connection must be made with minimum length conductors having maximum surface areas. Wide straps or
brackets rather than leadwires are preferred. Be careful to verify that mechanically tightened joints along the ground
path, such as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coatings and
are protected against mating surface corrosion.
b
2000 VA maximum connected load to the RM/EC7890 Assembly.
c
See Tables 4 and 5 for device load combinations.
d
Requires 220-240 to 120 Vac, 10 Va minimum stepdown transformer to drive the shutter. Not applicable for
C7061A1020, C7061A1079 or C7061F1003.
Pilot Fuel 8
C
B
F
F
D
D
D
A
4.5A ignition
50 VA Pilot Duty
plus 4.5A ignition.
Table 3. Terminal Ratings.
Description
Ratings (RM7890A,B,C)
a
120 Vac (+10%/-15%), 50 or
60 Hz (±10%).
120 Vac, 1A pilot duty.
120 Vac.
120 Vac.
120 Vac, 4.5A ignition.
60 to 220 Vac, current limited. 60 to 220 Vac, current limited.
120 Vac, 0.5A (RM7890B).
Table 4. Combinations for Terminals 8, 9, and 10.
F
F
F
No Load
F
D
No Load
B
180 VA ignition plus motor
valves with: 660 VA inrush,
360 VA open, 250 VA hold.
RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
b
c
c
c
Main 9
No Load
No Load
A
A
A
A
A
C
2A Pilot Duty.
5
Ratings (EC7890A,B)
220-240 Vac (=10%/-15%), 50 or
60 Hz (±10%).
220-240 Vac, 1A pilot duty.
220-240 Vac, 5A (maximum).
220-240 Vac, 4A at P.F. = 0.5, 20A
inrush.
220-240 Vac, 4A at P.F. = 0.5, 20A
inrush.
220-240 Vac, 4A at P.F. = 0.2.
220-240 Vac (EC7890B only).
Ignition 10
D
65 VA Pilot Duty plus motor
valves with: 3850 VA inrush,
700 VA Open, 250 VA hold.
d
F
32-00157-03