Honeywell 7800 Series Installation Instructions Manual page 8

Relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

RM7890A,B/EC7890A,B 7800 SERIES RELAY MODULES
L1
(HOT)
L2
1
MASTER
SWITCH
LED
DISPLAY
BURNER
START
OPERATING
CONTROLLER
AND LIMITS
FLAME
SIGNAL
1
120V, 50/60 HZ (RM7890) 220-240, 50/60 HZ (EC7890) POWER
SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
INSTALL A LINE VOLTAGE CONTROLLER IN SERIES WITH THE
LIMITS. IF USING A LOW VOLTAGE CONTROLLER IS
DESIRABLE, INSTALL AN EXTERNAL RELAY WITH THE N.O.
CONTACTS IN SERIES WITH THE LIMITS. THE LOW VOLTAGE
RELAY COIL WILL BE IN THE LOW VOLTAGE CONTROLLER
CIRCUIT. NOTE THAT IT MAY BE NECESSARY TO PROVIDE
AN EXTERNAL LOW VOLTAGE TRANSFORMER.
3
DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
4
TERMINAL 22 IS ONLY ON THE RM/EC7890B.
5
WHEN USING RM/EC7890A OR B; INSTALL AN EXTERNAL
RELAY TO SWITCH THE F LEAD. THE RELAY MUST HAVE
GOLD-CLAD OR GOLD-FLASH CONTACTS AND A LINE
VOLTAGE COIL. POWER THE RELAY COIL FROM THE Q7800
SUBBASE TERMINAL 8. CONNECT THE RELAY CONTACTS
BETWEEN THE F LEAD OF THE DETECTOR AND THE F
TERMINAL OF THE Q7800 SUBBASE.
Fig. 2. Wiring subbase and operating sequence chart for RM/EC7890.
32-00157-03
LINE VOLTAGE
ALARM
2
BURNER
CONTROLLER/LIMITS
INTERMITTENT
PILOT/IGNITION
MAIN FUEL
VALVE(S)
IGNITION
FLAME DETECTOR
7
6
00
SAFE-
INITIATE
STANDBY
START
POWER
POWER
POWER
LIMITS AND BURNER CONTROL CLOSED
SAFE START CHECK
8
Q7800
FOR DIRECT SPART IGNITION
G
12
(OIL OR GAS)
10
L2
13
14
3
(L1)
8
4
15
9
16
5
17
6
3
7
18
8
19
20
9
21
10
4
F
22
5
00
20
4/10
8
PFEP
MFEP
4 OR 10 SEC
RUN
POWER
POWER
POWER
PILOT
PILOT
PILOT
FLAME
FLAME
FLAME
MAIN
MAIN
MAIN
ALARM
ALARM
ALARM
10
IGNITION
9
8
INTERMITTENT PILOT
MAIN VALVE
9
3
TO
FLAME PROVING
6
USING EC7890, A 220-240 VAC TO 120 VAC, 10 VA MINIMUM
STEP-DOWN TRANSFORMER (NOT PROVIDED) MUST BE
USED TO DRIVE THE SHUTTER (C7012E,F; C7061; C7076A,D
DETECTORS). NOT APPLICABLE FOR C7061A1020, C7061A1079,
C7061F1003
SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING.
7
8
RM7890A1031 PFEP IS 30 SECONDS FIXED. RM7890B1030 PFEP IS
10 SECONDS FIXED.
9
MAIN FUEL VALVE IS ENERGIZED AND IGNITION (TERMINAL 10) IS
TURNED OFF DURING PFEP ONCE FLAME IS PROVEN.
EXCEPTIONS:
RM7890A1031/A2031 HAS A FIXED 30 SECOND PFEP
RM7890A1031/A2031 HAS A FIXED 30 SECOND PFEP
RM7890B1030/B2030 HAS A FIXED 10 SECOND PFEP
RM7890A1064/A2064, RM7890B1055/B2055 AND EC7890B1028/B202
JR1 INTACT – 10 SECOND FIXED PFEP, IGNITION
(TERMINAL 10) SHUTS OFF AT 6 SECONDS.
JR1 CLIPPED – 4 SECONDS FIXED PFEP, IGNITION
(TERMINAL 10) SHUTS OFF AT 2 SECONDS.
IGNITION
TRANSFORMER
L2
MAIN VALVE
STANDBY
POWER
9
6
S S C

Advertisement

Table of Contents
loading

Table of Contents