Impulse voltage withstand
test, test type
All circuits mutually except
serial interface
Insulation type of inputs and outputs
Signal inputs (current)
Signal inputs (voltage)
Power supply
Binary inputs and binary/relay
outputs
Serial interface
Analog inputs and analog
outputs
Reference conditions
Input current I
i
Input voltage V
i
Frequency
Waveform
Ambient temperature T
Power supply voltage V
Warm-up time
External fields
according IEC 60688 and
IEC 60255-5
5 kV; 1.2 / 50 µs
Reinforced,
max. 600 V AC, Cat II or
max. 300 V AC, Cat III
Protective impedance,
max. 600 V AC, Cat II or
max. 300 V AC, Cat III
Reinforced,
max. 230 V AC/250V DC, Cat II
Reinforced,
max. 230 V AC/250V DC, Cat II
Optical isolated
Optical isolated
The stated error limits apply for
reference conditions
I
± 1%
IN
V
± 1%
IN
45 ... 65 Hz
AC, harmonic distortion ≤ 5%
73.4 °F ± 1.8 °F (23 °C ± 1 °C)
A
V
± 1%
H
HN
≥ 15 min
no
17