General Purpose Communication; Led Indication; Hardware Reset And Software Reset - Hitachi EHV+ Series Applications Manual

Iec 61131-3 compliant plc
Table of Contents

Advertisement

3.14.4 General purpose communication

Besides Modbus-RTU function, EH-SIO supports general purpose communication same as CPU port.
Add "SysCom" library by clicking "Add library" on Library manager. Only the difference from CPU port is COM port
number. Be sure to set the same COM port number as "EH-SIO configuration" window. Refer to 3.15.3 Serial
communication for further information.

3.14.5 LED indication

MB and MS LED: When CPU has no application (user program) or wrong COM port setting or "None" assigned,
LNK, MB, HP and MS LED will light up. If correct COM port setting is downloaded, all of the LED will turn off.
(Even EH-SIO works in Modbus-RTU mode, internal setting of EH-SIO is always general purpose mode. For this
reason, MB and MS LED do not light.)
CDE LED: Even if correct COM port setting is downloaded, CDE LED will light up without cable connected
because DR signal is expected to be high in RS-232C port.

3.14.6 Hardware reset and Software reset

When the reset button is pressed while communication, the communication is aborted since EH-SIO is initialized. This
is hardware reset operation. Make stop and run to recover the communication.
Instead of that, SysComPurge command is able to initialize EH-SIO. This is software reset function.
Chapter 3
LNK ...
Link mode
Watch dog timer error
WDE ...
MDE ...
Module error
CDE ...
Command error
SD1/2 ...
Sending data
RD1/2 ...
Receiving data
MB1/2 ...
Modbus mode
HP1/2 ...
Hi-Protocol mode
MS1/2 ...
Modbus Master
422 ...
RS-422 port enabled
3 – 43
General Specifications