3.13 Modbus-TCP/RTU

3.13.1 Introduction
Supported function codes are shown in the below table.
16#
10#
0x01
01
Read Coils
0x02
02
Read Discrete Inputs
0x03
03
Read Holding Registers
0x04
04
Read Input Registers
0x05
05
Write Single Coil
0x06
06
Write Single Register
0x0F
15
Write Multiple Coils
0x10
16
Write Multiple Registers
0x17
23
Read/Write Multiple Registers
X = Supported, - = Not supported
Modbus command processing is executed in bus cycle tack, which is configured in PLC settings of Device as below.
You can specify any existing IEC tasks. If the bus cycle task is <unspecified>, task with the shortest cycle time is
taken.
N o t e
If Modbus-RTU or TCP function is needed, be sure to use EHV-CPU1025 or higher model because Modbus libraries
require about 100KB of user program memory.
Function code
Modbus-TCP Master
Modbus-RTU Master
CPU
Modbus-TCP Slave
X
X
X
X
X
X
X
X
X
3 – 32
EH-SIO
Modbus-RTU Master
-
X
-
X
X
X
X
X
-
X
X
X
-
X
X
X
X
X