Hitachi EHV+ Series Applications Manual page 32

Iec 61131-3 compliant plc
Table of Contents

Advertisement

Chapter 2
Specifications
(5) EH-XAH16
Specification
Input type
Number of inputs
Input voltage
Input current
Input impedance
Operating
ON voltage
voltage
OFF voltage
Input response
OFF
ON
time
ON
OFF
Insulation system
Input display
External connection
Number of inputs / common
Internal current consumption
Terminal configuration
[1]
[10]
[2]
[11]
[3]
[12]
[4]
[13]
[5]
[14]
[6]
[15]
[7]
[16]
[8]
[17]
[9]
[18]
Screw for
fixing
No.
Signal
name
[1]
0
[2]
1
[3]
2
[4]
3
[5]
4
[6]
5
[7]
6
[8]
7
[9]
C
[10]
8
[11]
9
[12]
10
[13]
11
[14]
12
[15]
13
[16]
14
[17]
15
[18]
C
EH-XAH16
AC input
16
200 to 240V AC (170 to 264V AC)
4.3 to 8.0mA (200V AC / 50Hz)
Approx. 32kΩ (50Hz) / Approx. 27kΩ (60Hz)
164V AC minimum
40V AC maximum
15ms maximum
25ms maximum
Photo-coupler insulation
Green LED
Removable type screw terminal block (M3)
16 (1 common, 2 terminals)
50 mA maximum
Diagram of Internal circuit
0
15
C
2 – 22
LED
Internal circuit

Hide quick links: