Specifications
EH-CUE
Terminal
configuration
RESET
CH2
CH1
16
1
CN1
30
15
EH-CUE
Note: Pin No. defined in EH-CUE does not accord with pin No. defined by the connector maker.
No.
CH2
No.
CH1
16
N.C.
1
Vin A
17
N.C.
2
A (+)
18
N.C.
3
A (-)
19
N.C.
4
Vin B
20
N.C.
5
B (+)
21
N.C.
6
B (-)
22
N.C.
7
Vin M
23
N.C.
8
M (+)
24
N.C.
9
M (-)
25 to 27 N.C.
10 to 12 N.C.
28
N.C.
13
Y0
29
N.C.
14
Y1
30
N.C.
15
Com1
2 – 76
Meaning of signal
Connects to a 12 to 24V DC power supply at
using voltage input.
Connects (+) polarity at using differential input.
Phase A
Connects an open collector signal at using
voltage input.
Connects (-) polarity at using differential input.
Connects to a 12 to 24V DC power supply at
using voltage input.
Connects (+) polarity at using differential input.
Phase B
Connects an open collector signal at using
voltage input.
Connects (-) polarity at using differential input.
Connects to a 12 to 24V DC power supply at
using voltage input.
Connects (+) polarity at using differential input.
Marker
Connects an open collector signal at using
voltage input.
Connects (-) polarity at using differential input.
Connect nothing.
Coincidence output. Connects to the other input.
Output
Coincidence output. Connects to the other input.
(-) common for coincidence output