Appendix D • Vission 20/20 Communication Table
Ethernet
TM
Modbus
Vilter
IP
Address
Address
Address
126
N56:13
40513
127
N57:0
40550
128
N57:1
40551
129
N57:2
40552
130
N57:3
40553
131
N57:4
40554
132
N57:5
40555
133
N57:6
40556
134
N57:7
40557
135
N57:8
40558
136
N57:9
40559
137
N57:10
40560
138
N57:11
40561
139
N57:12
40562
140
N57:13
40563
141
N57:14
40564
142
N57:15
40565
143
N57:16
40566
144
N57:17
40567
145
N58:0
40570
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Data
Command Name
Type
Force to local control
INT
Compressor Control
Setpoints
Setpoint #1 (Suct.
F-INT
Press, Proc Control,
Disch. Press)
Cap Inc Time Interval
F-INT
Setpoint #1
Cap Inc Proportional
F-INT
Band Setpoint #1
Cap Dec Time Interval
F-INT
Setpoint #1
Cap Dec Proportional
F-INT
Band Setpoint #1
Setpoint #2 (Suct.
F-INT
Press, Proc Control,
Disch. Press)
Cap Inc Time Interval
F-INT
Setpoint #2
Cap Inc Proportional
F-INT
Band Setpoint #2
Cap Dec Time Interval
F-INT
Setpoint #2
Cap Dec Proportional
F-INT
Band Setpoint #2
Cap Inc Pulse Time
F-INT
Setpoint #1
Cap Inc Dead Band
F-INT
Setpoint #1
Cap Dec Pulse Time
F-INT
Setpoint #1
Cap Dec Dead Band
F-INT
Setpoint #1
Cap Inc Pulse Time
F-INT
Setpoint #2
Cap Inc Dead Band
F-INT
Setpoint #2
Cap Dec Pulse Time
F-INT
Setpoint #2
Cap Dec Dead Band
F-INT
Setpoint #2

Auto Cycle

Start(Suct. Press/Proc
F-INT
Control/Disch. Press)
Setpoint #1
Value
1 = To local
Higher
Lower
Mode
Range
Range
Read-Write
Read-Write (-15.0,
(200.0,
-100.0,
150.0,
-15.0)
400.0)
Read-Write 0.5
5.5
Read-Write 0.5
20.0
Read-Write 0.5
5.5
Read-Write 0.5
20.0
Read-Write (-15.0,
(200.0,
-100.0,
150.0,
-15.0)
400.0)
Read-Write 0.5
5.5
Read-Write 0.5
20.0
Read-Write 0.5
5.5
Read-Write 0.5
20.0
Read-Write 0.5
5.5
Read-Write 1.0
50.0
Read-Write 0.5
5.5
Read-Write 1.0
50.0
Read-Write 0.5
5.5
Read-Write 1.0
50.0
Read-Write 0.5
5.5
50.0
Read-Write 1.0
Read-Write (-15.0,
(200.0,
-100.0,
150.0,
-15.0)
400.0)