Download Print this page

Troubleshooting - Trane 4TTR4A Series Installer's Manual

Advertisement

|nsta||er's
Guide
NOTE:
A 3/16" Allen wrench is required to open liquid line service
valve. A I/4" Open End or Adjustable
wrench is required to
open gas line valve. A 3/4" Open End wrench is required
to
take off the valve stem cap.
9. The liquid line shut-offvalve
can now be opened.
Remove
shut-off
valve cap. Fully insert hex wrench
into the stem
and backout counterclockwise
until valve stem just touches
rolled edge (approximately
five [5] turns) observing
WARNING
statement
on page 3. See Figure 4.
10. Replace liquid service pressure
tap port cap and valve
stem cap. These caps MUST
BE REPLACED
to
prevent
leaks.
Replace valve stein cap and pressure
tap
cap finger tight, then tighten
an additional
1/6 turn.
11. The gas valve can now be opened.
Open the gas valve by
removing
the shut-off valve cap and turning
the valve
stem 1/4 turn eounterelockwise,
using
1/4" Open End or
Adjustable
wrench.
See Figure 5.
12. The gas valve is now open for refl'igerant
flow. Replace
valve stem cap to prevent
leaks. Again, these caps
MUST
BE REPLACED
to prevent
leaks.
Replace valve
stem cap and pressure
tap cap finger tight, then tighten
an additional
1/6 turn.
See Figure 5.
If refl'igerant
lines are longer than
15 feet and!or a
diff>rent
size than recommended,
it will be necessary
to
adjust
system refl'igerant
charge
upon completion
of
installation.
See unit Service Facts.
F. ELECTRICAL
CONNECTIONS
When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility of
electric shock.
1. Power wiring and _'ounding
of equipment
must
comply
with local codes.
2. Power supply must agree with equipment
nameplate.
3. Install
a separate
disconnect
switch at the outdoor
unit.
4. Ground
the outdoor unit per local code requirements.
5. Provide flexible electrical
conduit
whenever
vibration
transmission
may create a noise problem within
the
structure.
6. The use of color coded low voltage wire is recommended
to simplify connections
between
the outdoor unit, the
thermostat
and the indoor unit.
Table I -- NEC Class II Control Wiring
24 VOLTS
WIRE SIZE
MAX. WIRE LENGTH
18 AWG
150 FT
16 AWG
225 FT.
14 AWG
300 FT.
7. Table 1 defines maximum
tota!
length of low voltage
wiring from outdoor unit, to indoor unit, and to thermostat.
8. Mount the indoor thermostat
in accordance
with instruc-
tion included
with the thermostat.
Wire per appropriate
hook-up diagram
(included
in these instructions).
G. COMPRESSOR
START UP
After all electrical
wiring is complete,
SET THE THERMO-
STAT SYSTEM
SWITCH
IN THE OFF POSITION
SO
COMPRESSOR
WILL NOT RUN, and apply power by
closing the system
main disconnect
switch.
This will activate
the compressor
sump heat (where used).
Do not change the
Thermostat
System
Switch until power has been applied
for
one (1) hour. Following
this procedure
will prevent
potential
compressor
overload
trip at the initial start-up.
H. OPERATIONAL
AND
CHECKOUT
PROCEDURES
Final phases
of' this installation
are the unit Operational
and
Checkout
Procedures
which are found in this instruction
(see
page 8). To obtain proper performance,
all units
must be
operated
and charge adjustments
made in accordance
with
procedures
found in the Service Facts.
I. ELECTRIC
HEATERS
Electric
heaters,
if used, are to be installed
in the air han-
dling device according
to the instructions
accompanying
the
air handler
and the heaters.
d. START CONTROL
Some models have quick start components
which are fhctory
installed.
For models that do not have fhctory installed
start
components,
provisions
are made for a field installed
start kit
accessory.
When adding an accessory,
follow the instructions
provided
with the kit.
K. OUTDOOR
THERMOSTAT
An outdoor
thermostat
TAYSTAT250B
may be field installed.
For data, see wiring diagram
attached
to unit and instruction
sheet packaged
with outdoor thermostat.
L. SEACOAST
SHIELD
Units installed
within
one mile of salt water, including
seacoasts
and inland
waterways,
require
the addition
of
BAYSEAC001
(Seacoast
Kit) at the time of installation.
IMPORTANT:
See Limited Warranty information in Use and Care Manual
M. TROUBLESHOOTING
TROUBLESHOOTING
CHART -- WHAT TO CHECK
SYSTEMFAULTS
REFRIGERANT
CIRCUIT
ELECTRICAL
Compressor &OD Fan DoNotStart
Compressor WillNotStartButOD FanRuns
OD FanWon't S tart
Compressor Nt_ms ButWon't S tart
Compressor Cycles onIOL
ID Blower Won'tStart
P PrimaryCauses S Sec0ndary Causes
4
18-AC51 D6-1

Advertisement

loading

This manual is also suitable for:

4ttr4b series4ttr4018b4ttr4024b4ttr4030a4ttr4036a4ttr4042a ... Show all