Unit Operating Voltage Range
Volts
Phase
Hz
Minimum Circuit Ampacity
Minimum Overcurrent Protection Device
Size
Maximum Overcurrent Protection Device
Size
No.
Volts
Phase
RPM
HP, Compressor 1
Amps (RLA), Comp. 1
Amps (LRA), Comp. 1
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No.
Volts
Phase
HP
Amps (FLA, each)
Amps (LRA, each)
No.
Volts
Phase
HP
Amps (FLA, each)
Amps (LRA, each)
ELECTRICAL DATA
ELECTRICAL DATA - RHPDZT SERIES
120ACF
120ACG
120ACH
187-253
187-253
187-253
208/230
208/230
208/230
3
3
3
60
60
60
54
57
58
70
70
70
80
80
90
1
1
1
200/230
200/230
200/230
3
3
3
3450
3450
3450
10
10
10
32.6
32.6
32.6
240
240
240
2
2
2
208/230
208/230
208/230
1
1
1
1/2
1/2
1/2
2.5
2.5
2.5
5.6
5.6
5.6
1
1
1
208/230
208/230
208/230
3
3
3
2
3
3
7.7
10.4
12
47
74.5
74.5
120ADF
120ADG
120ADH
414-506
414-506
414-506
460
460
460
3
3
3
60
60
60
26
27
28
30
35
35
40
40
40
1
1
1
460
460
460
3
3
3
3450
3450
3450
10
10
10
14.8
14.8
14.8
130
130
130
2
2
2
460
460
460
1
1
1
1/2
1/2
1/2
1.5
1.5
1.5
3.1
3.1
3.1
1
1
1
460
460
460
3
3
3
2
3
3
3.9
5.2
6
24
38.1
38.1
120AYF
120AYG
120AYH
517-632
517-632
517-632
575
575
575
3
3
3
60
60
60
19
20
20
25
25
25
25
30
30
1
1
1
575
575
575
3
3
3
3450
3450
3450
10
10
10
11.1
11.1
11.1
93.7
93.7
93.7
2
2
2
575
575
575
1
1
1
1/2
1/2
1/2
1.1
1.1
1.1
1.5
1.5
1.5
1
1
1
575
575
575
3
3
3
2
3
3
2.5
3.5
3.5
19
20
20
37