Download Print this page

Vaillant turboMAX plus 2 E Series Installation Instructions Manual page 36

Air flue duct

Advertisement

FITTING THE APPLIANCE FLUE OUTLET ADAPTER TO THE BOILER
1
7
Fig. 2.2
36
Fig. 2.1
3
4
2
5
6
Appliance flue outlet adaptor
Accy. No.: 303 814
Ø 60/100 to Ø 80/125
Contents of the accessory:
• Adaptor including condensate
discharge connection
• 48 mm Air duct clamp
• Condensate trap
• Condensate discharge tube
• 2 Plastic rachet clips
• Support clip
• Before installing the adaptor onto
the boiler outlet select and fit the
correct restrictor (page 33).
For turboMAX boilers fit the
restrictor into the bottom of the
adaptor (page 34).
For thermoCOMPACT boilers refer
to the installation instructions
supplied with the boiler for details
on fitting the restrictor.
• Fit the adaptor to the boiler by
inserting the spigot of the adaptor
(1) into the flue socket on the
boiler and secure using the air
duct clamp provided (7).
• Drill two holes 3 mm Ø through
the air duct clamp and secure the
air duct clamp to the boiler using
the screws provided.
Note: Because of the high efficiency
of turboMAX, thermoCOMPACT and
aquaPLUS boilers it is likely that
condensate will form in the flue
system when a long flue run is used.
A condensate discharge connection is
provided on the adapter to remove
any condensate that forms in the flue.

Advertisement

loading