Hide thumbs Also See for Front 30:

Advertisement

Quick Links

INSTALLER: Leave this manual with appliance
CONSUMER: Retain this manual for future reference.
Installation & servicing of this appliance MUST be performed by a qualified NFI certified technician.
MASSACHUSETTS: The piping and final gas connection must be performed by a licensed plumber gas
fitter in the state of Massachusetts.
Modern Gas Fireplaces – Linear Fireplaces
FLARE
FIREPLACES POWER VENT INSTALLATION GUIDE
[Flare Fireplaces PV system] v 4.6
NOTICE

Advertisement

Table of Contents
loading

Summary of Contents for Flare Fireplaces Front 30

  • Page 1 Installation & servicing of this appliance MUST be performed by a qualified NFI certified technician. MASSACHUSETTS: The piping and final gas connection must be performed by a licensed plumber gas fitter in the state of Massachusetts. Modern Gas Fireplaces – Linear Fireplaces FLARE FIREPLACES POWER VENT INSTALLATION GUIDE [Flare Fireplaces PV system] v 4.6...
  • Page 2: Table Of Contents

    CONTENTS SAFTEY INFO AND WARNINGS............................4 FLARE FIREPLACES – FRAMELSS IN EVERY WAY ....................... 4 SAFETY ..................................... 5 MANUAL MODEL LIST & INFORMATION ......................... 5 POWER VENTING OVER VIEW ............................6 POWER VENT DRAWINGS ..............................6 HORIZONTAL END OF LINE POWER VENT DRAWING ..................... 6 .....................................
  • Page 3 BURNER MAINTENANCE ............................. 31 VENT MAINTENANCE ..............................31 DOUBLE GLASS FANS ..............................31 MAINTENANCE LOG ..............................31 WARRANTY POLICY ............................... 32...
  • Page 4: Saftey Info And Warnings

    FLARE FIREPLACES – FRAMELSS IN EVERY WAY Flare Fireplaces is where innovation, quality and luxury come together to form new ideas. By combining superior raw materials, contemporary design, creative technology and a frameless way of thinking, we have created a full line of direct-vent fireplaces that are luxurious, simple to operate and efficient.
  • Page 5: Safety

    To simplify the installation and operation, all models above share the same gas valve system, remote, gas connection, glass type. All warnings and instructions apply to all models. Flare Fireplaces Power Vent system must only be connected to M&G 3x5 venting system.
  • Page 6: Power Venting Overview

    POWER VENTING OVERVIEW In the event of a vent route that is unsupported based on the Gravity Vent Tables shown in the Flare Install Manual, Flare Fireplaces may use a power vent to accommodate any extremely long, or negative degree venting routes. The 3 power vent options allow the fireplace to operate in vent conditions that would not be possible without the powered fan.
  • Page 7: Horizontal End-Of-Line Power Vent Framing Dimensions

    HORIZONTAL END-OF-LINE POWER VENT FRAMING DIMENSIONS ROUGH OPENING CUT-OUT DIMENSIONS: 13 ½ W x 14 ½ H...
  • Page 8: Horizontal Power Vent Part List

    HORIZONTAL POWER VENT PART LIST HORIZONTAL POWER VENT PART LIST: ITEM NUMBER PART NUMBER DESCRIPTION W-F-08 PV External Cover W-F-14 PV Board Cover W-F-19 PV Board Holder W-F-17 M4 Stainless Steel Screws Draft Switch HUBA control to measure fan pressure Electronic Board Electronic Board Cooling Fan...
  • Page 9: Vertical End Of Line Power Vent Drawing

    VERTICAL END OF LINE POWER VENT DRAWING ROOF Exhaust Outlet (Sold Separately )
  • Page 11: Vertical Power Vent Part List

    VERTICAL POWER VENT PART LIST VERTICAL POWER VENT PARTS LIST: ITEM NUMBER PART NUMBER DESCRIPTION Housing of Exhaust Blower - Vertical The whole block for vertical power vent Fan | 03 + 04 Main Fan Holder Exhaust Blower Main Exhaust Fan Fan | 08 Inner upper cover for exhaust outlet Draft Switch...
  • Page 12: In-Line Power Vent Drawing

    IN-LINE POWER VENT DRAWING (Sold Separately )
  • Page 13: In-Line Power Vent Parts List

    IN-LINE POWER VENT PARTS LIST IN-LINE POWER VENT PARTS LIST: ITEM NUMBER PART NUMBER DESCRIPTION FanExNet External Cover Cooling Fan Exhaust Blower Main Fan Draft Switch HUBA Control FanExDish Electronic Board Holder House of Exhaust Blower In-Line In-Line Whole Block...
  • Page 14: Vent Adapter Conversion

    VENT ADAPTER CONVERSION In the event a fireplace is shipped with a standard collar and needs to be converted to support a CVS 3x5 collar, follow the steps below: 1. Remove the 4x6/5x8 Vent adapter from the top of the fireplace as shown in the pictures below:...
  • Page 15 2. Install 3x5 Vent adapter: a. Attach the 3inch Female (inner) part first as shown in step1, then tighten the screws as shown in step 2. b. Use 3mm ceramic fiber paper to isolate the vent adapter as shown in steps 1 and 4. c.
  • Page 16 3. Place the 5 Inch Male Adapter in place and tighten down screws to secure to unit.
  • Page 17: Clearances To Power Vent

    Minimum 18-inch x 18-inch access panel required for service. b. The Flare Fireplaces Power Vent must be in an area with a minimum 8 cubic feet of free air space to keep the component operating temperature cool. In addition, the access panel must be louvered to allow for a minimum of 75 sq.
  • Page 18: Multiple Vertical Termination Points

    MULTIPLE VERTICAL TERMINATION POINTS Exhaust Outlet • If using decorative cap cover/s, this distance may need to be increased. Refer to the installation instruction supplied the decorative cap cover. • In a staggered installation with both gas and wood or fuel oil termination, the wood or fuel oil termination cap must be higher than.
  • Page 19: Vent Termination Clearances

    VENT TERMINATION CLEARANCES *12 inches (30 cm) min. Clearances above grade, veranda, porch, deck, or balcony *12 inches (30 cm) min. Clearance to window or door that may be opened 12 inches (30 cm) min. Clearance to permanently closed window recommended to prevent condensation on window 30 inches (76 cm) min.
  • Page 20: Vent Restrictor Setup

    • Flame lacks movement. RESTRICTOR POSITION NEEDS TO BE CLOSED MORE IF THE FLAME HAS THE FOLLOWING CHARACTERISTICS: • Flame height is low. • Flame has excessive movement DOCUMENT ANY CHANGE TO THE RESTRICTOR SETTING CONTACT FLARE FIREPLACES FOR SUPPORT IF NEEDED...
  • Page 21: Power Vent Electrical Connection

    POWER VENT ELECTRICAL CONNECTION • All Flare Fireplaces PV system are connected to the Fireplace with a low voltage 6V cable. • In addition, the Power Vent system will require a separate 15A power source connected to it. The electrical line to the Power Vent must supply 120 Volts, 60 Hz, and 15 Amps (maximum draw).
  • Page 22: Fireplace Electrical Drawing (With Power Vent - Maxitrol)

    FIREPLACE ELECTRICAL DRAWING (WITH POWER VENT - MAXITROL) Low Volatage Communication Wire. Green, Black, White...
  • Page 23: Sit Proflame 2 Connections

    SIT PROFLAME 2 CONNECTIONS...
  • Page 24: Fireplace Electrical Drawing (With Power Vent- Sit Promflame 2)

    FIREPLACE ELECTRICAL DRAWING (WITH POWER VENT- SIT PROMFLAME 2) Low Volatage Communication Wire. Green, Black, White...
  • Page 25: Power Vent Board Electrical Drawing

    Power Vent is functioning properly. Contact Flare Fireplaces for any additional questions.
  • Page 26: Venting

    VENTING To calculate the vent runs use the following tables and instructions. Please note that power vent runs are model (burner) specific. Use the tables below to calculate the restrictor setting. A MINIMUM LENGTH OF VENTING IS REQUIRED BETWEEN THE APPLIANCE. DO NOT INSTALL POWER VENT SYSTEM IF THE MINIMUM LENGTH IS BELOW 20FT.
  • Page 27 FLARE-60 (FLARE-FF, FLARE-ST, FLARE-RC, FLARE-LC, FLARE-DC, FLARE-RD) Run Length Restrictor Setting Burner Type Unit Type 20--28 Flare 60 28--40 Flare 60 40--52 Flare 60 52--64 Flare 60 64--76 Flare 60 76--88 Flare 60 88--100 Flare 60 FLARE-70 (FLARE-FF, FLARE-ST, FLARE-RC, FLARE-LC, FLARE-DC, FLARE-RD) Run Length Restrictor Setting Burner Type...
  • Page 28: Connecting 3X5 Pipe

    CONNECTING 3X5 PIPE The Flare Power Vent system uses DuraVent 3x5 CVS vent system. The DuraVent CVS vents includes a lock system and a silicone gasket on every side of the vent. Make sure you follow the DuraVent CVS installation manual: http://duravent.com/docs/product/l916.pdf Please follow the vent marking for directing of vent flow.
  • Page 29: Replacement Parts

    REPLACEMENT PARTS See below for flare replacement part list. • Please contact your fireplace dealer to purchase any replacement part. • Please make sure to provide the description and part number. • Please make sure to use a certified installer for any service related to your fireplace. PART NUMBER PART NAME PART NUMBER...
  • Page 30: Appendix

    APPENDIX • It is recommended that a qualified service technician perform a routine inspection at the beginning of each heating season. • Disconnect power before attempting maintenance or repair of the fireplace. • Installation and maintenance must be performed by an authorized qualified installer, service agency or gas supplier.
  • Page 31 • Turn off the fans and install back the trim and glass. MAINTENANCE LOG Flare Fireplaces – Maintenance log Following document should be used by the service technician. A copy should be kept with the technician and owner for future...
  • Page 32 • It is the responsibility of the installer to ensure the appliance is firing as per the rating plate. • Any part that is found in our judgment to be defective shall be repaired, replaced or refunded at Flare Fireplaces option.

Table of Contents