D+H LSC-M Series Instructions For Use Manual

Lift smoke control
Table of Contents

Advertisement

LSC-M
Lift Smoke Control
System for Lift Shaft and
Staircase Smoke Vent
Instruction for use

Advertisement

Table of Contents
loading

Summary of Contents for D+H LSC-M Series

  • Page 1 LSC-M Lift Smoke Control System for Lift Shaft and Staircase Smoke Vent Instruction for use...
  • Page 3: Table Of Contents

    3.0 System Overview .....................8 Functional Principle........................9 Why Smoke Suction?......................10 Wiring Plan Lift Shaft......................11 Wiring Plan Staircase......................12 Cable for D+H Smoke and Heat Vent Systems ..............13 Line lenghts and Cross sections ..................13 Project Planning of Smoke Suction System.................14 Tube System ....................15 Mounting of Tube System ....................16...
  • Page 4 Index Central Appliance LSC 44-M4 ...............23 Mounting Place LSC 44-M4 ....................23 Inside Design of Control Center ...................24 SHEV Control Panel of Type RZN 4404-M VdS ..............25 View motherboard RZN 4404-M VdS...................26 Standard Connection with RT 43-H/-N .................27 Parallel Connection of RT 43-H/-N ..................28 Codification of Group 1 and 2 ....................29...
  • Page 5: Lift Shaft Smoke Vent

    Consequently energy can be saved, ventilation controlled and smoke vent ensured in case of fire. With LSC D+H offers a special system, which will provide smoke vent of lift shafts in case of fire by Legal Aspects Legal Aspects Energy Saving Regulation EnEV 10/2007 §...
  • Page 6: One System Many Advantages

    Possible whistling sounds will be additionally The D+H system LSC avoids unnecessary losses avoided, caused by a too high flow of air. of energy, because a permanent opening in the top...
  • Page 7: Solutions For Every Case Of Application

    Solution for every Application Detection of a fire will occur by a smoke suction The integrated SHEV staircase system will system in the lift shaft and a smoke detector monitor the adjacent staircase. The smoke staircase. detector, installed at the top end area of the staircase, will detect the fire smoke in the staircase For the lift shaft...
  • Page 8: Introduction To Shev Systems

    Introduction to SHEV Systems Smoke and heat vent systems (SHEVs) are very escape and rescue routes will be kept free for the important elements of structural preventive fire fire brigade. Consequential damages by protection. conflagration gases are reduced and therefore considerable material assets are often protected Smoke and heat vent systems are appliances of from destruction.
  • Page 9: Maintenance

    D+H authorized expert companies have been specially trained by D+H for carrying out expertly and once a year, maintenance must be carried out this maintenance, and they get automatically the by specialist companies.
  • Page 10: System Overview

    System Overview Lift Shaft Staircase Acoustical + optical rain detector alarm devices * VRS 10* Domelight with drive window on lift shaft with drive < or > Louvre window Smoke with drive detector in lift shaft Signal contact to BMS/ MSR Signal contact (measurement to Lift control...
  • Page 11: Functional Principle

    Functional Principle Smoke recognition Opening of the smoke vent flap Evacuating travels Prevention of of lift car further lift car travels and activation of the staircase smoke vent 09/48 LSC 44-M4...
  • Page 12: Why Smoke Suction

    Why Smoke Suction? Suction opening Suction tube Domelight Control panel Smoke detector Ventilation button Smoke vent button RT 43-N Window drive Smoke detector 10 Smoke vent button RT 43-LSC 11 Smoke vent button RT 43-H Taking samples of air through smoke suction over smoke detector in front of the landing entrance.
  • Page 13: Wiring Plan Lift Shaft

    Wiring Plan Lift Shaft drive control see cable panel wiring table 230VAC 230V 50Hz JY (St) Y not possible to switch off 2x2x0,6 24VDC JY (St) Y 2x2x0,6 JY (St) Y JY (St) Y 2x2x0,6 2x2x0,6 fire JY (St) Y detector 2x2x0,6 external control...
  • Page 14: Wiring Plan Staircase

    Wiring Plan Staircase drive control see cable panel wiring table to further ones 230VAC to further ones 230V 50Hz JY (St) Y not possible to switch off 2x2x0,6 24VDC JY (St) Y 2x2x0,6 fire JY (St) Y 2x2x0,6 detector contact key-operated external control vent button...
  • Page 15: Cable For D+H Smoke And Heat Vent Systems

    Cable for D+H Smoke and Heat Vent Systems The smoke vent control panel is designed for Detector Cables (Line): opening smoke vent devices, which operate by The detector cables are monitored for short circuit thermal ascending force and by automatic fire and for break.
  • Page 16: Project Planning Of Smoke Suction System

    Project Planning of Smoke Suction System Regulations The following project planning regulation is orientated to the system limitations of TITANUS MICRO- SENS. In this connection, respective national regulations of the states in the valid version each must be observed. The project planning must be adapted to these standards. In Germany With CEA-Requirement DIN VDE 0833 part 1 and 2 “alarm systems for...
  • Page 17: Tube System

    Tube System The tube system serves for a defined air sampling A simplified project planning will be applied in from the monitoring area and consists of different equipment protection and in conveniences of small components. dimensions. Recirculation in shaft Shaft Ceiling Air Filter max.
  • Page 18: Mounting Of Tube System

    Mounting of Tube System The tube system shall be put together according to the requisition by the project and with observance of the project planning guidelines. Cut tubes to length (pipe cutter or pipe shears 38mm/ metal cutting saw) Suction tube (PVC) (optional available) Clean tube R-2519, R-3218, R-4019)
  • Page 19: Mounting Of Reflux Valve At Suction Tube End

    Mounting of Reflux Valve at Suction Tube End Cut tubes to length (pipe cutter or pipe shears 38mm / metal cutting saw) Clean tube street fittings! Suction tube (PVC-red) R-2519, R-3218, R-4019 Suction tube halogen free (optional available) ABSR-2518, ABSR-3220, ABSR-4025 Burring Burring After cleaning,...
  • Page 20: Pipe Clamps

    - If the tube system does not meet the project whether an air throughput is available on the planning guidelines, as described here, individual suction openings. because of structural facts, it must be separately calculated by D+H for the respective conditions. 18/48 LSC 44-M4...
  • Page 21: Tube Project Planning Guideline

    Tube Project Planning Guideline Tube length < 15m Tube length 15-25m Tube length 25-40m 2 borings 4 borings 6 borings (pre-drill Ø 10mm) (pre-drill Ø 10mm) (pre-drill Ø 10mm) Foil Foil Foil Ø 4,6 Ø 3,2 Ø 2,0 Foil Foil Foil Ø...
  • Page 22: Suction Openings

    Suction Openings Chose set-up of suction opening (suction boring) requisition of the project and with observing of the and position of tube system according to the project planning guidelines. Burring bore 10mm hole burring outside and inside 10mm 90° Afterwards clean boring area from fat and dust over entire tube surfaces...
  • Page 23: Air Filter Lf-Ad

    Air Filter LF-AD Mounting 1. Unscrew swivel nut of PG29-screw fittings 2. Stick suction tubes into both sides 3. Screw down again swivel nuts 4. Screw filter housing directly on wall with housing lower part Observe flowing-through direction of the filter with mounting! (label on housing outside) Exchange of Air Filters 1.
  • Page 24: Free-Blowing Device

    The compressed-air device will be operated with 230V. Only with this efficient compressed-air device is a building-up of a sufficient pressure volume possible for best possible cleaning. The compressed-air device is available at D+H with the designation Pipe•Clean. 22/48 LSC 44-M4...
  • Page 25: Central Appliance Lsc 44-M4

    Central Appliance LSC 44-M4 Mounting Place LSC 44-M4 minimum 20cm Air Filter Control panel 23/48 LSC 44-M4...
  • Page 26: Inside Design Of Control Center

    Inside Design of Control Center Connection suction tube and recirculation Test connection Stop Central connecting pcb valve LSM 44 LSM 44 MICRO-SENS RZN 4404-M 2 x accu type 3 Gehäusegröße (BxHxT) 600x600x210mm Smoke SHEV suction control device system Accumulators for emergency supply 24/48 LSC 44-M4...
  • Page 27: Shev Control Panel Of Type Rzn 4404-M Vds

    SHEV Control Panel of Type LSM 44-M4 The SHEV- control panel of type RZN 4404-M VdS transmitters, will process them and run open and is the core piece of an electric motor driven smoke closed the electric drives in smoke vent devices. and heat vent system.
  • Page 28: View Motherboard Rzn 4404-M Vds

    RZN 4404-M IN : 230VAC / 240VA OUT : 24VDC / max. 4A 12.345.67-65.43 - 123456 Temp. -5°C..40°C D+H Mechatronic - Germany - +49 40 605 65 0 1 2 3 4 5 6 7 8 ground short fuse fuse mains...
  • Page 29: Standard Connection With Rt 43-H/-N

    Standard Connection with RT 43-H/-N The connection for the external components of the staircase SHEV-system will be connected to line 2 and group 2 on the central PCB RZN 4404-M. (The LSM-module for the lift shaft smoke vent is connected to line 1 and group 1) 27/48 LSC 44-M4...
  • Page 30: Parallel Connection Of Rt 43-H/-N

    Parallel Connection of RT 43-H/-N Fire detector Smoke vent button Smoke vent button Typ** RT 43-H RT 43-N 10k * 10kW 10k * RM / RT * shunt connection RZN 4404-M (Line 2) by customer 28/48 LSC 44-M4...
  • Page 31: Codification Of Group 1 And 2

    Codification of Group 1 and 2 Following functionings can be set with DIP switch S2/ S4 on motherboard. ON SAB ON SAB 1 2 3 4 1 2 3 4 5 6 7 8 1 2 3 4 1 2 3 4 5 6 7 8 Group 1 Group 2 Switch 1 on ON =...
  • Page 32: Codification Of Lin E 1 And 2

    Codification of Line 1 and 2 Following functionings can be set with DIP switch S1/ S3 on motherboard. ON SAB ON SAB 1 2 3 4 1 2 3 4 5 6 7 8 1 2 3 4 1 2 3 4 5 6 7 8 Line 1 Line 2 Switch 1 on ON =...
  • Page 33: Codification Of Control Panel

    Codification of Control Panel Following functionings can be set with DIP switch S6 motherboard. 0°C 605 65 0 1 2 3 4 5 6 7 8 Control Panel Switch 1 on ON = Line 2 on group 3 Line 2 is also effective on group 3 Switch 1 on OFF = Group 3 is independent of line 2 Switch 2 on ON...
  • Page 34: Factory Preset Of The Dip-Switch

    5.10 Factory preset of the DIP-Switch Control Group Panel S6 S2/ S4 Line S1/ S3 5.11 Delivery Condition Conf. at Delivery starting condition Switch Function Two-smoke detectors dependency Smoke detector alarm only to be reset in control panel Line fault = Alarm Idle OPEN-running time limitation Ventilating time limitation...
  • Page 35: Lsc-System For Ventilating Purposes As Well

    5.12 LSC-System for ventilation purposes as well The system facilitates to use the SHEV-system for The possibility of ventilation will be automatically ventilation purposes as well. This will be effected blocked in any kind of malfunction. via ventilation button or a floating contact in neutral Possibility of selecting different variants via position of another control system.
  • Page 36: Smoke Suction System Of Type Micro-Sens

    ® 5.14 Smoke Suction System of Type MICRO-SENS Content Detector module for recognition of smoke aerosols Airflow detector for monitoring of tube system on break and choking (the airflow detector is integrated in detector module) Suction unit for transport of air samples to detector module. LED does not lighten LED lightens Display...
  • Page 37: Plug And Play-Initiation-Airflow Alignment

    - ventilator voltage can be adjusted according to the regulations, ventilator and ventilator power The diagnosis tool is optionally available at D+H pack are working normally. Mechatronic under the designation DIAG 3. Airflow initialization will be immediately Testing of TITANUS MICRO·SENS...
  • Page 38: Central Module Lsm 44

    5.16 Central Module LSM 44 - Integrated LSC-module for user specific Furthermore, following functions are available modifications - timer for emergency supply time of the - function selection via DIP-switches with pilot RAS-Sytem (0 3 6 72 hours) indicators - timer for siren alarm - all required connecting terminals are centrally flap will open automatically in case of power...
  • Page 39: Dip-Switch S1

    5.18 DIP Switch S1 DIP Switch 1 on ON Alarm smoke detector on first evacuating level will release SHEV-alarm Alarm smoke detector on first evacuating level will be only indicated as DIP Switch 1 on OFF floating in neutral position DIP Switch 2 on ON Alarm smoke detector on first evacuating level will be indicated on low tension side for acoustic alarm devices.
  • Page 40: Connection Signalling Lift / External Signals

    5.20 Connection Signalling Lift / External Signals To lift control Signal to BMS SHEV SHEV Mal- SHEV SHEV Mal- Alarm Alarm function Alarm Alarm function Lift first main Lift first main shaft evacution shaft evacution level level Signals lift External signals Floating contacts in neutral position With floating contacts in neutral position for...
  • Page 41: Connection Bms/ Rm/ Rt

    * Terminal resistors for line monitoring: ** Fire detectors They are pinched in control panel for transport. Only D+H system approved detectors must be Take it off there and connect according to plan. used Terminal resistors must remain at binder RM 1,2, when no fire detector or external control exists.
  • Page 42: Connection Rem/ Lt/ Mot/ Bz/ Bl

    5.22 Connection REM/ LT/ MOT/ BZ/ BL Key-operated vent button Drive SLT 42U-SD branch box 2 resistors 47k or terminal module thermal detector THE 4 REM 42 blue last brown flashing Alarm- light siren LSM 44 40/48 LSC 44-M4...
  • Page 43: Smoke Vent Device / Connecting Elements

    Different operational elements and significance in case of fire. The well tried D+H detectors are available for release and operation of SHEV-drives, triggered from the LSC-system will the LSC-system.
  • Page 44: Informations For Mounting Of Louvres / Domelight

    Informations for Mounting of Louvre/ Domelight - Alterations or repairs on the system must be Domelight or louvre must be handled by only carried-out by the manufacturer. trained specialists from the roofer- and window Alterations of the system, taken on one's own, building trade.
  • Page 45: Key-Operated Vent Button Slt 42

    Key-operated vent button SLT 42 The key-operated vent button serve to manually open and close a ventilation group. SLT 42A-SD SLT 42U-SD - key-operated vent button in - key-operated vent button in surface moistureproof design flush mounted design for profile semicylinder with integrated LED-visual display OPEN - with integrated LED-visual display OPEN - mounted in recessed 55mm flush socket, flush...
  • Page 46: Fire Detector Fo 1362

    Fire detector FO 1362 The detector consists of the base with the connections and the detector upper part with evaluation unit. Detector base and upper part are connected via a bajonet catch (a quarter turning). The smoke detector must be horizontally placed at the highest point underneath the ceiling in proximity of the landing entrance on the first main evacuation level.
  • Page 47 Connection to Control Panel fire detector type ** 10k * last LSM 44 first or panultimate ** fire detectors only D+H system approved detectors must be used LSM 44 45/48 LSC 44-M4...
  • Page 48: Smoke Vent Button Rt 43-H-Lsc

    With plug screws 4,5x40mm diogonal or direct on 55m flush socket with 2 screws. Housing colour Standard: deep orange (RAL 2011) according to VdS 2592. However, locally variant, other colours can be demanded. LSM 44 Please consult your D+H partner. 46/48 LSC 44-M4...
  • Page 49: Smoke Vent Button Rt 43-H/-N

    With plug screws 4,5x40mm diogonal or direct on 10kW 55m flush socket with 2 screws. Housing colour Standard: deep orange (RAL 2011) according to VdS 2592. RM / RT However, locally variant, other colours can be RZN 4404-M demanded. Please consult your D+H partner. 47/48 LSC 44-M4...
  • Page 50: Alarm Series B/Se 24

    Alarm Siren B/SE 24 Alarm siren LSM 44 Technical Data Power supply : 10-28V/ 0,03A Loudness : 80-116dB, adjustable Dimensions : ø 92mm, height 75mm Protective system : IP 54 LSM 44 Colour : red 6.10 Flashing light BL 41 flashing - grey with orange dome light...
  • Page 52 Consulting • Service • Sales D+H Mechatronic AG Georg-Sasse-Str. 28-32 • 22949 Ammersbek/Hamburg, Germany Phone: +49 40-605 65-0 Fax: +49 40-605 65-222 • info@dh-partner.com www.lsc.dh-partner.com • © 2005 D+H Mechatronic AG, Ammersbek...