Pipe Clamps; Checking Of Tube System - D+H LSC-M Series Instructions For Use Manual

Lift smoke control
Table of Contents

Advertisement

4.3

Pipe Clamps

Fasten tubes with
pipe clamps without
rubber ply.
Lay tube system firmly.
It must neither hang sagging
nor must it be possible that it
is moved out of place.
4.4
Checking of Tube Systems
- for leakages (e.g. by damages)
- for faulty connections
- for correct project planning of suction openings
- check with critical applications safe detection
with response tests apart from this check,
whether an air throughput is available on the
individual suction openings.
18/48
LSC 44-M4
Air Filter
(with high
variations
in temperature
max. 30cm)
max. 80cm
Smoke
suction
device
SHEV-control panel
For the
first clamp
after tube connection at TITANUS
MICRO SENS ,
which
does not allow linear extension.
E
10
9
D
8
7
6
C
5
4
B
3
2
A
1
Plastic pipe clamps of type NG 23 are
used as standard for installation of the
tube system (Ø 25mm). They do not
allow linear extensions.
- The ventilator voltage can be infinitely
increased from 9V (standard) up to 13.5V in
order to increase the velocity of air flow in the
tube system in critical areas.
- If the tube system does not meet the project
planning guidelines, as described here,
because of structural facts, it must be
separately calculated by D+H for the respective
conditions.
of the tube system,
®
a type has to be used,

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lsc 44-m4

Table of Contents