ST_ControllerParameter
Table 14: Description
Name
Unit
iMode
none
iReactionOnFail
none
ure
fYTune
none
fYStable
none
dwAlarmSupp
none
tCtrlCycleTime
s
tTaskCycleTime
s
fWMin
°C
fWMax
°C
fWVeloPos
°C/s
fWVeloNeg
°C/s
fWStartUp
°C
tStartUp
s
bStartUpRampin
none
g
fWStartUpVeloP
°C/s
os
fWStartUpVeloN
°C/s
eg
fYMin
none
fYMax
none
fYManual
none
fYOnFailure
none
tPWMCycleTim
s
e
tFilter
s
bFilter
none
bEnablePreCont
none
roller
bEnableZones
none
bEnableCVFilter
none
iFilterType
none
iControllerType
none
TempLow
°C
TempLowLow
°C
TempHigh
°C
TempHighHigh
°C
TempAbsoluteHi
°C
gh
TempAbsoluteL
°C
ow
TC3 Temperature Controller
Value range
Description
INT
Controller operating mode (1 = heating, 2 = cooling, 3 =
heating & cooling) (see below)
INT
Parameterisable reaction to errors (see below)
LREAL
Control value during the self-tuning (normally 100%)
LREAL
Control value during the settling phase (normally 0%)
DWORD
Masks out the alarms (see below)
TIME
Controller's sampling time. In the course of the sampling
time the controller re-calculates the control value.
TIME
Task cycle time. The FB is called with this time interval.
LREAL
Minimum set value.
LREAL
Maximum set value.
LREAL
Rate of rise (of ramp).
LREAL
Rate of fall (of ramp).
LREAL
Set value at start-up.
TIME
Time with the fWStartUp set value.
[TRUE,FALSE]
Switches on ramping during the start-up phase.
LREAL
Rate of rise (of ramp) during the start-up phase.
LREAL
Rate of fall (of ramp) during the start-up phase.
LREAL
Minimum value of the control variable.
LREAL
Maximum value of the control variable.
LREAL
Control value in manual operation.
LREAL
Control value in case of error (parameterisable).
TIME
Cycle time of the PWM signal.
TIME
Time constant of the actual value filter (first order P-T1
filter)
[TRUE,FALSE]
The actual value filter is actuated if TRUE.
[TRUE,FALSE]
Switches pre-controller on.
[TRUE,FALSE]
Switches open loop characteristic on until close to set
value.
[TRUE,FALSE]
Switches on control value filter following the main
controller.
ENUM
Selection of a filter type for the control value filter
following the main controller (see below)
ENUM
Selection of a control algorithm (see below)
LREAL
Relative lower temperature limit in the first band.
LREAL
Relative lower temperature limit in the second band.
LREAL
Relative upper temperature limit in the first band.
LREAL
Relative upper temperature limit in the second band.
LREAL
Absolute upper temperature limit.
LREAL
Absolute lower temperature limit.
Version: 1.1
PLC libraries
35