Beckhoff TwinCAT 3 Manual page 26

Table of Contents

Advertisement

PLC libraries
Name
Unit
General
Parameters
iMode
none
iReactionOnFailure
none
bSelCtrlParameterS
none
et
dwAlarmSupp
none
tCtrlCycleTime
tTaskCycleTime
tuning parameters
iTuningMode
tTuneStabilisation
fEndTunePercentHe
ating
fYTuneCooling
fYStableCooling
fScalingFactor
none
setpoint
parameters
fWMin
fWMax
bEnableSoftStart
none
bEnableRamping
none
fWStartUp
tStartUp
bStartUpRamping
none
fWStartUpVeloPos
fWStartUpVeloNeg
fWVeloPos
fWVeloNeg
actual value
parameters
tFilter
bFilter
none
deadband
parameters
bDeadband
none
fEDeadband
control value
parameters
fYMin
none
fYMax
none
fYManual
none
fYOnFailure
none
26
Range
INT
INT
BOOL
DWORD
s
TIME
s
TIME
°C
E_CTRL_TuneMo
de
s
TIME
%
(L)REAL
°C
(L)REAL
°C
(L)REAL
(L)REAL
°C
(L)REAL
°C
(L)REAL
BOOL
BOOL
°C
(L)REAL
s
TIME
[TRUE,FALSE]
°C/s
(L)REAL
°C/s
(L)REAL
°C/s
(L)REAL
°C/s
(L)REAL
s
TIME
[TRUE,FALSE]
[TRUE,FALSE]
°C
(L)REAL
(L)REAL
(L)REAL
(L)REAL
(L)REAL
Description
Controller operating mode (1 = heating, 2 = cooling, 3 =
heating & cooling) (see below)
Parameterisable reaction to errors (see below)
TRUE = external parameter set, FALSE = internal
parameter set (from tuning)
Masks out the alarms (see below)
Controller's sampling time. In the course of the sampling
time the controller re-calculates the control value.
Task cycle time. The FB is called with this time interval.
Selects how tuning should be done (see below)
Waiting time (stabilisation of process) until step for tuning
is switched on.
percent of setpoint when controller stops tuning and waits
for switching to closed loop control
Control value for tuning step in cooling mode.
Control value for stabilizise process before cooling tuning
starts.
Scaling factor: if only heating tuning was done cooling
parameters are heating parameter*scaling factor
Minimum value of the control variable.
Maximum value of the control variable.
FALSE = no soft start, TRUE = soft start
FALSE = no ramping, TRUE = ramping
Setpoint while soft start phase
Waiting time in soft start phase
Enables ramping in soft start phase
Rate of rise (of ramp) during the start-up phase.
Rate of fall (of ramp) during the start-up phase.
Rate of rise (of ramp).
Rate of fall (of ramp).
Time constant of the actual value filter (first order P-T1
filter)
The actual value filter is actuated if TRUE.
TRUE = Deadband on, FALSE = Deadband off
Size of deadband in °C
Minimum value of the control variable.
Maximum value of the control variable.
Control value in manual operation.
Control value in case of error (parameterisable).
Version: 1.1
TC3 Temperature Controller