Toshiba Carrier RBM-Y0611F4PUL Installation Manual page 12

Multi port flow selector unit
Hide thumbs Also See for Carrier RBM-Y0611F4PUL:
Table of Contents

Advertisement

Available languages

Available languages

U1 U2
U1 U2
Indoor unit
A
B
A
B
L2
L1
Remote control
Connectable number of indoor units per group control connection
The number of maximum connectable indoor units through a single remote control is 8 units.
Indoor unit
No.1
No.2
No.3
A
B
A
B
A
B
(A.B)
Remote control
A B
A B
A B
A B
FS unit
In case that two remote controls are connected, the number of maximum connectable indoor units is 7 units.
Indoor unit
No.1
No.2
No.3
A
B
A
B
A
B
(A.B)
Remote control
(Main)
A B
A B
A B
A B
FS unit
* The maximum connection number of remote control per group is 2 pcs.
The communication wiring and AC 208 / 230 V wires cannot be parallel to contact each other and cannot
be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise
or other factor.
EN-21
U1 U2
A
B
L3
A B
A B
A B
A B
FS unit
No.4
No.7
No.8
A
B
A
B
A
B
No.4
No.7
A
B
A
B
Remote control
(Sub)
CAUTION
11
Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the Flow Selector unit.
• Keep a margin (Approx. 3.9" (100mm)) on a wire to hang down the electrical control box at servicing.
• The low-voltage circuit is provided for the communication wires. (Do not connect the high-voltage circuit)
1
Loosen the cover mounting screws (4 positions) of the electrical control box, and then
remove the cover.
2
Attach the conduit pipe with a lock nut.
3
The cable clamp (accessory) is installed in the underside of the Flow Selector unit.
4
Connect the power supply wire and communication wires to the terminal blocks of the
electrical control box.
5
Tighten screws of the terminal block securely, and fi x the wires with cord clamp attached
to the electrical control box. (Do not apply tension to the connecting section of the terminal
block.)
6
Mount the cover of the electrical control box so that it does not pinch the wires.
q Connecting power supply wire and communication wires
Clamp the communication wire
Clamp all cables
Detail (a)
For each communication wire, attach the Clamp fi lter (accessory) as the picture below.
2.0" to 2.4"
(50 to 60 mm)
Attach round
shaped terminal
(locally procured)
Clamp fi lter
(Accessory)
(a)
L1 L2
Cable clamp
Power supply terminal block
(Accessory)
A B
Communication
Terminal on PCB for Communication wiring
wire
Binding band
(Accessory)
Clamp fi lter (Accessory)
Hook 2 nails
Communication wire
(locally procured)
1 turn
Ground screw
Cable clamp
Conduit pipe
Lock nut
Power supply wire
EN-22

Advertisement

Table of Contents
loading

This manual is also suitable for:

Carrier rbm-y0611f6pul

Table of Contents