D-Script And Global D-Script Errors - Digital Equipment Pro-face GP2000 Series User Manual

Table of Contents

Advertisement

7.5.7 D-Script and Global D-Script Errors

The following error messages are displayed when D-Scripts and Global D-Scripts
are not configured properly. The GP-2300/2301 Series unit displays the error
message on the bottom at the GP screen.
D-Script
Global D-Script Global D-Script Error (***)
The following table lists the numbers assigned to (***) in the above error mes-
sages. Error Nos. "001" and "002" are displayed at power-on, and Error Nos.
"003" and "004" are displayed when an error occurs during the function process-
ing.
No.
001
002
003
004
GP-2300/2301 Series User Manual
Chapter 7 - RUN Mode and Errors
Error Message
D-Script Error (***)
Description
T he total number of Global D-Scripts exceeds the limit.
T he maximum number of Global D-Scripts is 32. Note
that functions are included in the counts.
T he total of all devices in the Global D-Script exceeds
the limit of 255 devices.
Either the function being called does not exist, or that
function has caused an error.
Function cannot be nested more than 10 levels.
Applicable
Script
Global D-Script
Global D-Script
D-Script
Global D-Script
D-Script
Global D-Script
7-23