SPECIFICATIONS

General
For a complete list of all terminals and their
description of their functions, see Table 4 on pg.4.
NOTE:
All terminal blocks capable of carrying either
low voltage or line voltage are orange-colored.
The product package includes a plastic bag
containing additional, removable terminal blocks.
Power Supply Terminals
Power is supplied to the controller via a removable
terminal plug (Color coded grey, terminal 1 and 2).
CAUTION
Do not mix-up power terminal block
(terminal 1 to 3, Grey color) with
BACnet MS/TP terminal block (terminal
4 to 6, black color) located adjacent to
each other. Interchanging the terminals
will damage the controller.
See also section "Power supply" on pg. 9
Power Supply
20-30 VAC at 50/60 Hz, Class 2
transformer
Power
Controller with all
Consumption
connected loads: 100 VA
maximum
Controller only: 20 VA
maximum
Auxiliary
20 VDC ± 10% at 75 mA
Output
Ambient Environmental Limits
-40 °F to 150 °F (-40 °C to 66 °C)
Storage
Operation
32 °F to 122 °F (0 °C to 50 °C)
Humidity
5% to 95% RH., non-condensing
Differential Pressure Sensor
Bi-Directional
Operating Range: 0 to 2.0 in. H
Actuator Specifications
Rotation Stroke
Torque Rating
Runtime for 90°
rotation
COMPACT VAV CONTROLLER WEB-VA423B24N – INSTALLATION INSTRUCTIONS
O (0 to 500 Pa).
2
95° ± 3° for CW or CCW
opening dampers
44 in-lbs (5 Nm)
108 seconds at 50 Hz
90 seconds at 60 Hz
Real Time Clock
Operating Range: 24 hour, 365 day, multi-year
calendar including day of week and configuration
for automatic daylight savings time adjustment to
occur at 2:00 a.m. local time on configured start
and stop dates.
Power Failure Backup: 72 hours.
Accuracy: ±3.5 minute per month at 77 °F (25 °C)
Digital Relay Outputs (DO)
Voltage Rating: 24 VAC at 50/60Hz
Current Rating: 1.5 A continuous, and 3.5 A (AC
RMS) for 100 milliseconds per DO channel.
Analog outputs (AO)
Analog outputs can be individually configured for
current or voltage.
Analog Current Outputs
Current Output Range: 4.0 to 20.0 mA DC
Output Load Resistance: 550
Analog Voltage Outputs
Voltage Output Range: 0.0 to 10.0 VDC
Maximum Output Current: 10.0 mA DC
Universal Inputs (UI) Circuits
See table below for the UI circuit specifications.
Table 3: Universal inputs types and characteristics
Input Type
Room/Zone
Discharge Air
Outdoor Air
Temperature
Outdoor Air
Temperature
Resistive
Input
Voltage Input
Discrete Input
Pulse Input
a
a
One Universal Input (UI-1) on the WEB-
VA423B24N is user selectable as a fast digital
pulse meter.
3
maximum
Ω
Sensor
Operating Range
Type
20k
NTC
-40 °F to 199 °F
Ω
(-40 °C to 93 °C)
PT1000
-40 °F to 199 °F
(IEC751
(-40 °C to 93 °C)
3850)
Generic
100
to 100K
Ω
Transducer
0-10 VDC
Controller
Dry Contact
0-10 VDC without
Closure
pull-up resistor,
External 499 Ω
resistor required to
measure 0-20 mA
Counter/M
Maximum
eter
Frequency: 15 Hz
Minimum Pulse
Width: 33 ms.
31-00362-01
Ω