Mitsubishi Heavy Industries KXZ Series Service Manual page 44

Vrf inverter multi-system, outdoor units
Hide thumbs Also See for KXZ Series:
Table of Contents

Advertisement

Code
Contents of display
No.
C73
Compressor error causes 1
C74
Compressor error causes 2
C75
Compressor error causes 3
< Information for unusual counter >
C80
Counter · Current cut (CM1)
Counter · Power transistor overheat (CM1)
C82
C84
Counter · Compressor startup failure (CM1)
Counter · Anomalous compressor by loss of
C86
synchronism (CM1)
Counter · Communication error between inverter
C88
PCB and outdoor unit control (CM1)
C90
Counter · Anomalous FMo1
C91
Counter · Anomalous FMo2
C92
Counter · Indoor-outdoor communications error
C93
Counter · Outdoor unit CPU reset
< The other >
C96
Data reset
C97
Program sub-version
C98
Program POL version
(Spare)
C99
Auto send display
< 7-segment software input >
< User setting >
Switching to operation priority
P01
P02
Outdoor fan snow protection control
Outdoor fan snow protection control ON time
P03
setting
P05
Silent mode setting
P06
CNZ1 function assignment
Data display
Minimum
range
unit
Displays No. of the error detection of which effect is the strongest among
0~127
1
those occurred from the start of operation after the power on
Displays No. of the error detection of which effect is stronger secondly
0~127
1
among those occurred from the start of operation after the power on
Displays No. of the error detection of which effect is stronger thirdly
0~127
1
among those occurred from the start of operation after the power on
1
EEPROM memory. Resettable.
0~255
1
0~255
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
EEPROM memory. Resettable.
0~255
0~255
EEPROM memory. Resettable.
0~991
0.00~9.99
0.01
0: First push priority
0: (Factory default)
1: Last push priority
1
2: Director mode
0, 1, 2, 3
3: Operation mode capacity priority
0: (Factory default)
0: Invalid
1: Valid
0, 1
30: (Factory default)
Changes to 10, 30, 60, 90 ... 600.
30
10,30~600(sec)
0: (Factory default)
1
0 ~ 9
0: (Factory default)
1
See page 27
0 ~ 9

-
5
-
-
-
'14 • KX-SM-221
'14 • KX-SM-221
Remarks

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kxzp seriesFdc224kxzpe1Fdc280kxzpe1

Table of Contents