GE EntelliGuard AKR30S-800A Installation Manual page 44

R3 & r6 type retrofill circuit breakers 800-5000a
Table of Contents

Advertisement

15. Adjust the nut to get a spacing of 0.766—0.797 inch between the top of the upper retainer and the
bottom of the flat washer.
16. Tighten the jam nut to lock in the adjustment.
17. Clean finger assemblies, if necessary, with a clean, lint-free rag and isopropyl alcohol or acetone.
18. Be sure to apply a thin film of Mobilgrease 28 (D50HD38) to the contact areas which slide onto the
switchgear stabs (See Figure 33, Step 2). This product is available in a 1-oz tube, GE Part #193A1751P1.
Figure 33 summarizes the steps for working with the primary contacts.
Figure 33. Steps in Exploded Views
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual