2. Identify the type of programmer disconnect assemblies to be installed on the Retrofill breaker.
The programmer disconnect assembly to be assembled depends upon the type of legacy breaker that is
being replaced. These are as follows:
AKR30/30H/50/50H/T50H/30/75/100/125L—In these, the programmer disconnect is mounted on the
left side wall of the Retrofill breaker.
AKR30S—In these, the programmer disconnect is mounted on the right side wall of the Retrofill
breaker.
Programmer disconnect assemblies are available in two configurations, namely:
12-pin configuration—If the legacy LVS has a 12-pin programmer disconnect in use, the same can be
used with the Retrofill breaker. In this case, only the breaker side programmer disconnect assembly
on the breaker needs to be installed. The numbers for the programmer disconnects are mentioned
below.
P/N 10105385G1
P/N 10105651G1
P/N 10105385G2
P/N 10108733G1
P/N 10108732G1
P/N 10108733G2
19-pin configuration—If the legacy LVS doesn't have a 12-pin programmer disconnect configuration,
and the customer chooses to install a programmer disconnect, then the 19-pin programmer
disconnect assembly needs to be installed in the compartment and the breaker.
10108733G1
10108732G1
10108733G2
10108801G1
10109176G1
10108801G2
3. If applicable, remove the existing compartment side programmer disconnect assembly.
The programmer disconnect assembly must be removed, if:
A 9-pin manual programmer disconnect assembly is installed in the cabinet as a result of conversion
kit.
A 24-pin programmer disconnect assembly is installed in the cabinet original MicroVersaTrip ~1979-
1984.
Customer chooses to replace a 12-pin configuration with a 19-pin configuration to Add RELT.
4. Before uninstalling the existing programmer disconnect assembly, verify that the wiring details match
the wiring numbers. Any changes or deviations need to be noted for use while installing the new
programmer disconnect.
5. Check that the compartment is de-energized and is safe to work in; and that the legacy breaker has been
removed from the cabinet.
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual
39
12-Pin Programmer Disconnect Breaker Side
PROG.DIS.ASSY, AKD8
PROG. DIS. ASSY
PROG. DIS. ASSY
19-Pin Programmer Disconnect Breaker Side
PROG.DIS.ASSY, AKD8
PROG.DIS.ASSY, AKR30S
PROG.DIS.ASSY, AKR75/100/125
19-Pin Programmer Disconnect Breaker Side
PROG.DIS.ASSY, AKD8
PROG.DIS.ASSY, AKR30S
PROG.DIS.ASSY, AKR75/100/125
19-Pin Programmer Disconnect Compartment Side
PROGRAMMER DISC ASSY
PROGRAMMER DISC ASSY
PROG.DIS.ASSY, AKR75/100/125
AKR30H/50H/T50H AKD8
AKR30S
AKR75/100/125
AKR30H/50H/T50H AKD8
AKR30S
AKR75/100/125
AKR30H/50H/T50H AKD8
AKR30S
AKR75/100/125
AKR30H/50H/T50H AKD8
AKR30S
AKR75/100/125
DEH41549 R05