VdS approval according to DIN EN 14637
6
Current requirements
The FSZ Basis provides a total output current of 400 mA. This output current can be completely
used for the required components of the hold-open system. The current required for the hold-open
system consists of the sum total of all currents of the components connected.
Example calculation:
The hold-open system comprises the following components:
Smoke switch
Electromagnetic door
retainer
Total current requirements
The total current must not exceed 400 mA. The current consumption of the various components of
the hold-open system is specified in the related product documents.
3 x ORS 142
2 x THM 425
146 mm x 146 mm x 60.5 mm
3 x 22 mA
2 x 63 mA
6 x M16 and 2 x M20
420 g
Z-x.x-xxxx
G 213091
66 mA
126 mA
192 mA
9