CAMDEN EMF-2 Installation Instructions Manual page 13

Multi-function timer

Advertisement

Press the exterior wall switch at door #1.
restroom
is
unoccupied
automatically.
Pot #2 adjusts the door hold-open
time (up to 30 seconds). If the restroom is occupied
and the Lock button has been pressed, then the door
will not open. (An Occupied light would be lit.)
After entering the restroom, push the nearest Lock
button. The EMF-2 will energize both electric locks
and remove both exterior Push switches from the
circuit.
To exit the Restroom, two options are available:
1. To have the door unlock and open automatically,
push the respective interior Wall switch.
also reset the EMF-2 for the next person to use.
2. Manual Use.
The door may also be used
manually.
To exit the restroom, turn the (lever)
handle and pull (push) the door open. The magnet
switch resets the unit into standby mode.
Occupied lights / LED's will extinguish.
Repeat the above procedure door #2.
function exactly as above.
Emergency Panic Switch (optional)
Should an emergency occur, and assistance from the
outside is required, the occupant can push a button
or ribbon switch to signal the EMF-2 (input #3).
When activated, the EMF-2 will unlock the door (and
optionally open the door). A maintaining type input is
required to keep the door held open.
Based on the settings of Dipswitch #'s 6 & 8 either
the doors will unlock only, or the last door used will
open,
or,
both
doors
simultaneously.
Further, Relay #4 is now activated, which can be
used to signal for assistance, sound an alarm –
whatever you choose. The installer can choose a
continuous or pulsing output, depending on the
settings of potentiometers # 4 & 5.
Emergency Time-out Feature
An added safety feature in the EMF-2 is the ability to
automatically reset to standby mode after a fixed
lock time of 15 minutes. The door will unlock, so that
personnel may enter the restroom. This feature is
engaged by turning dipswitch # 7 to
If not desired, simply leave dipswitch 7
If the
the
door
will
open
This will
The
It should
will
unlock
and
open
position.
ON
.
OFF
Section 3E________________
Set-up Instructions
2 / 3 door Airlock (Mode 5)
This function is designed to control up to 3 sets of
sliding, or swinging doors. The relay will allow only 1
door to be open at a time.
It accomplishes this by a Door Sense input, such as
a magnetic contact switch, located at each door. If
the Door Sense determines that a door is open, then
it will not allow a second door to open, but
remembers the request to open and allows it once
the first door has closed.
For 2-door airlocks, the installer can set up "Auto-
crossing" whereby after triggering one door, the
second door will activate after the first door closes.
(This
is
also
known
sequencing).
Should a door become stuck open, a Trouble signal
is output after 5 minutes. The EMF-2 also includes a
"Lock-down" input that resets the system and/or
disables all "Open" requests.
Step 1
Select
via the first 3 positions of the
MODE 5
dipswitch as shown below:
See diagram 1 for location of dipswitch, connectors,
& potentiometers.
Step 2
Dip Switch Options
Use of Relay 5 is optional, and set according to
dipswitches #4 & 5.
Push switch #6
ON
sequencing). In this Mode when input A is activated,
first door A opens, then when closed again, door B
opens in sequence.
Conversely, when input B is
activated, first door B opens, then when it is closed
again, door A opens sequentially.
cannot be used in "Auto-Mode". Selecting this mode
disables door C input and contact input.
Set dipswitch #7
for airlocks containing 2 doors
ON
only, or set to
for 3 doors. Dipswitch #8 has no
OFF
effect in this mode.
as
bi-directional
Off On
1
2
3
for "Auto Mode" (door
A third door
Page 13 of 19