CX-EMF-2 / EMF-2m
Multi-Function Timer
INSTALLATION INSTRUCTIONS
1. GENERAL DESCRIPTION
Camden's EMF-2 (EMF-2m or EMF-2ABM) is a microprocessor controlled multi-function relay. This all-in-one design replaces our
previous models EMF-1, EMF-1m or EMF-1ABM. The EMF-2 is designed for specialized applications such as ABM vestibules, one or two-
door restrooms in shared-use facilities, 2 – 5 door airlocks, and secure man-traps.
Dip switches let you choose the mode, and the unit automatically programs the inputs, outputs and potentiometers accordingly.
Removable terminal strips simplify wiring chores, and all adjustments are conveniently located on one end of the case.
IMPORTANT: Do not apply power to the unit until you have read the instructions fully and made the required adjustments.
2. INSTALLATION
Voltage
12/24V AC/DC
Current Draw
150mA @ nominal
Response Time
0.3 seconds
Mode Selector
via 3 dipswitches
Inputs
7 Dry Contacts, 1 Digital Input
Outputs
5 SPDT Relays, 1 Digital Output
Firmware
Verion A1-001
Relay Contact
3 Amps @ 20 VDC
Rating
5 pots, adjustable from 1 to 30 seconds
Time Delays
(depending on mode selected)
100,000 operations @ rated or
Electrical Life
500,000 operations @ 1/2 rated capacity
EMF-2: Double-sided foam tape or (2) #6 screws
Mounting
EMF-2M & EMF-2ABM: 4 x Metal screws &
anchors (provided)
EMF-2: Formed Plastic Housing
Enclosure
EMF-2M & EMF-2ABM: Beige Metal Cabinet
Dimensions
EMF-2
EMF-2M &
EMF-1ABM
In addition to the above, Model EMF-2 ABM includes a lockable
metal cabinet to house the relay. The cabinet is equipped with two
lighted push-switches - on to turn the relay power on or off, and the
other to control the DAY/NITE function.
Page 1 of 16
500mA @ maximum
7" H x 3" W x 7/8" D
(178mm x 76mm x 22mm)
12" H x 7-1/2" W x 3-3/4" D
(305mm x 191mm x 95mm)
Mounting
The EMF-2 should be mounted in a clean dry location out of direct
contact with the elements. Suitable locations include inside a
metal box, operator header, or above a false ceiling.
If placed on top of a header, ensure that unauthorized personnel
cannot tamper with the unit.
If used in an Airlock or Mantrap application, the relay may be
located at either door location, or, centrally to all doors.
You must bring wiring from all door actuators to this unit
(as well as the lock, operator, and door contact outputs
as appropriate).
The EMF-2 is also available in an attractive lockable metal cabinet
version (EMF-2m or EMF-2ABM), suitable for wall mounting.
Wiring
Wiring of this unit is dependant on the mode desired. Select
your intended application, then proceed to the section indicated.
Note: Do not wire Safety devices to the EMF-2. If installed, wire
your safety device directly to the operator control box.
IMPORTANT: Changes to the Mode and Out2 do not take
effect until a power reset. It is therefore best to make these
adjustments with the power turned off!
NOTE: We highly recommend the use of a regulated power
supply when powering equipment for barrier-free washroom
applications where the strike power may be maintained from
a few minutes to many hours. We offer a low-cost board-only
regulated power supply - CX-PS13 V2, which in turn can be
powered from a small 24VAC transformer, (or the auxiliary power
on the door control) and will supply clean, filtered & regulated
24 VDC power for the strike and EMF-2.

Advertisement

loading

Summary of Contents for CAMDEN CX-EMF-2

  • Page 1 INSTALLATION INSTRUCTIONS 1. GENERAL DESCRIPTION Camden's EMF-2 (EMF-2m or EMF-2ABM) is a microprocessor controlled multi-function relay. This all-in-one design replaces our previous models EMF-1, EMF-1m or EMF-1ABM. The EMF-2 is designed for specialized applications such as ABM vestibules, one or two- door restrooms in shared-use facilities, 2 –...
  • Page 3: Step 2 - Dip Switch Options

    CX-EMF-2 MULTI-FUNCTION TIMER I NSTA LLAT I O N I N S T RU C T I O N S 3. APPLICATIONS & SET-UP INSTRUCTIONS ABM Vestibule Control (Mode 1) Proceed to Section 3A - Page 3 2/3 Door Airlock w/ auto-crossing (Mode 5) Proceed to Section 3E - Page 13...
  • Page 5 CX-EMF-2 MULTI-FUNCTION TIMER I NSTA LLAT I O N I N S T RU C T I O N S The 7-pin Digital I/O strip provides either 12 VDC or 5 VDC on SECTION 3B - SET-UP INSTRUCTIONS Terminals 6 & 7 for lighting an “Occupied” LED. This output is present whenever the door is locked.
  • Page 7 CX-EMF-2 MULTI-FUNCTION TIMER I NSTA LLAT I O N I N S T RU C T I O N S Step 2 - Dip Switch Options After entering the restroom, push the Lock button. EMF-2 will (de)energize the electric lock momentarily to let the occupant...
  • Page 9 CX-EMF-2 MULTI-FUNCTION TIMER I NSTA LLAT I O N I N S T RU C T I O N S Step 3 - Connections SECTION 3D - SET-UP INSTRUCTIONS Refer to Diagram 5 for the following connections. Wire all input connections to the (removable) Input terminal strip 2-Door Restroom (Mode 4) (numbered 1-14).
  • Page 11 We suggest 15 minutes. The door unlocks, so that personnel may enter standard door contacts (ie.Camden Model #CX-MDC). the restroom. This feature is engaged by turning dipswitch #7 Make your connections to the relay output strip (numbered to ON position.
  • Page 13 We suggest and allows it once the first door has closed (the memory standard door contacts (ie. Camden Model #CX-MDC). Wire all feature may be disabled). contacts in series as shown in the diagram.
  • Page 15: Section 5 - Warranty

    EMF-2ABM) to be free from manufacturing defects for 3 years Step 4 - Adjustments from date of sale. If during the first 3 years the CX-EMF-2 / EMF-2ABM) fails to perform correctly, it may be returned In this application, you will use pots 1,2,3 & 5.