Section 1__________________
General Description
Camden model EMF-2 (EMF-2m or EMF-2ABM) is a
microprocessor controlled multi-function relay. This
all-in-one design replaces our previous models
EMF-1, EMF-1m or EMF-1ABM.
The EMF-2 is designed for specialized applications
such as ABM vestibules, one or two-door restrooms
in shared-use facilities, 2 – 5 door airlocks, and
secure man-traps.
Dip switches let you easily choose the mode, and the
unit automatically programs the inputs, outputs and
potentiometers accordingly.
Removable terminal strips simplify wiring chores, and
all adjustments are conveniently located on one end
of the case.
IMPORTANT: Do not apply power to the unit until
you have read the instructions fully and made the
required adjustments.
Section 2__________________
Installation
Mounting
The EMF-2 should be mounted in a clean dry location
out of direct contact with the elements.
locations include inside a metal box, operator header,
or above a false ceiling. If placed on top of a header,
ensure that unauthorized personnel cannot tamper
with the unit.
If used in an Airlock or Mantrap application, the relay
may be located at either door location, or, centrally to
all doors.
You must bring wiring from all door
actuators to this unit (as well as the lock, operator,
and door contact outputs as appropriate).
The EMF-2 is also available in an attractive lockable
metal cabinet version (EMF-2m or EMF-2ABM),
suitable for wall mounting.
Fax: 905-366-3378
Suitable
EMF-2 / EMF-2m
Multi-Function Timer
Installation Instructions
Ver. A1-001
MADE IN CANADA
Wiring
Wiring of this unit is dependant on the mode desired.
Select your intended application, then proceed to the
section indicated.
Note: Do not wire Safety devices to the EMF-2. If
installed, wire your safety device directly to the
operator control box.
IMPORTANT:
Changes to the Mode and Out2
do not take effect until a power reset. It is therefore
best to make these adjustments with the power
turned off!
NOTE:
We highly recommend the use of a
regulated power supply when powering equipment for
barrier-free washroom applications where the strike
power may be maintained from a few minutes to
many hours.
We offer a low-cost board-only
regulated power supply - CX-PS13 V2, which in turn
can be powered from a small 24VAC transformer, (or
the auxiliary power on the door control) and will
supply clean, filtered & regulated 24VDC power for
the strike and EMF-2.
APPLICATIONS
& SET-UP INSTRUCTIONS:
ABM Vestibule Control
(Mode 1) Proceed to section 3A
1 Door Unsecured Restroom
(Mode 2) Proceed to section 3B
1 Door Secured Restroom
(Mode 3) Proceed to section 3C
2 Door Unsecured Restroom
(Mode 4) Proceed to section 3D
2 / 3 Door Airlock (w/ auto-crossing)
(Mode 5) Proceed to section 3E
2 - 5 Door Airlock
(Mode 6) Proceed to section 3F
2 Door Man-trap
(Mode 7) Proceed to section 3G on Page 17
System Inspection Instructions
Technical Specifications, & Warranty
PAGE 1 OF 19
on Page 3
on Page 5
on Page 7
on Page 11
on Page 13
on Page 15
Page 18
Page 19

Advertisement

loading

Summary of Contents for CAMDEN EMF-2

  • Page 1 EMF-1, EMF-1m or EMF-1ABM. Note: Do not wire Safety devices to the EMF-2. If installed, wire your safety device directly to the The EMF-2 is designed for specialized applications operator control box.
  • Page 2 2 7/8" (72 mm) Side View NOTE: Pin 2 Connector. When connecting to Camden Card Reader in ABM Mode it is possible to read all cards by wiring the Blue wire to Pin 2, or only Cards beginning with a 4, 5, &...
  • Page 3: Setup Instructions

    Finally, connect 12 or 24 Volt AC or DC supply to A new feature of the EMF-2 is the ability to add an terminals 1 & 2 of the 2-pin Power Connector. “Emergency - Push-to-Lock” switch near the ATM (The terminals are not polarity sensitive).
  • Page 4 To have Relay 5 Mississauga, Ontario shadow another relay, set dipswitch L4W 2T7 as shown at right SCALE: NONE DRAWN BY: DGW DATE: 03/24/10 REVISED: ON ON EMF-2 Diagram 2, Typical ABM Vestibule Application FILENAME: EMF-2 Diagram 2.vsd DRAWING No: DRG-EMF-2_02...
  • Page 5 (it has been electronically de- See diagram 1 for location of dipswitch, connectors, activated). & potentiometers. A new option on the EMF-2 is the provision for an emergency “Lock Down” switch to be added. This IMPORTANT: Any changes Mode selector or Out2...
  • Page 6 DRAWN BY: DGW DATE: 03/24/10 REVISED: 06/08/10 RELAY 5 CHART OFF OFF To have Relay 5 EMF-2 Diagram 3, Single Door Restroom Application (unsecured) shadow another relay, set dipswitch as shown at right FILENAME: EMF-2 Diagram 3.vsd DRAWING No: DRG-EMF-2_03...
  • Page 7 The output can be maintained or pulsed. manually. To exit the restroom, turn the (lever) As an added safety feature, the EMF-2 can be set to handle and pull (push) the door open. The magnet automatically reset (and unlock) after 15 minutes switch resets the unit into standby mode.
  • Page 8 DRAWN BY: DGW DATE: 03/24/10 REVISED: 06/08/10 RELAY 5 CHART OFF OFF To have Relay 5 EMF-2 Diagram 4, Single Door Restroom Application (secured) shadow another relay, set dipswitch as shown at right FILENAME: EMF-2 Diagram 4.vsd DRAWING No: DRG-EMF-2_04...
  • Page 9 Emergency Time-out Feature terminals 1 & 2 of this terminal strip. An added safety feature in the EMF-2 is the ability to Finally, connect 12 or 24 Volt AC or DC supply to automatically reset to standby mode after a fixed terminals 1 &...
  • Page 10 DRAWN BY: DGW DATE: 03/24/10 REVISED: 06/08/10 RELAY 5 CHART OFF OFF To have Relay 5 EMF-2 Diagram 5, 2 Door (shared) Restroom Application shadow another relay, set dipswitch as shown at right FILENAME: EMF-2 Diagram 5.vsd DRAWING No: DRG-EMF-2_05...
  • Page 11 The 7-pin provides either 12V DC or Digital I/O strip As an added safety feature, the EMF-2 can be set to 5V DC on Terminals 6 & 7 for lighting “Occupied” automatically reset (and unlock) after 15 minutes LED’s. This output is present whenever the door is time.
  • Page 12 12 - 24 V AC/DC 5502 Timberlea Blvd Camden Door Controls Power Mississauga, Ontario L4W 2T7 SCALE: NONE DRAWN BY: DGW DATE: 03/24/10 REVISED: EMF-2 Diagram 6, 2 - 3 Door Airlock Application FILENAME: EMF-2 Diagram 6.vsd DRAWING No: DRG-EMF-2_06...
  • Page 13 A opens, then when closed again, door B opens in sequence. Conversely, when input B is An added safety feature in the EMF-2 is the ability to activated, first door B opens, then when it is closed automatically reset to standby mode after a fixed again, door A opens sequentially.
  • Page 14 5502 Timberlea Blvd Camden Door Controls Mississauga, Ontario 12 - 24 V L4W 2T7 AC/DC Power SCALE: NONE DRAWN BY: DGW DATE: 03/24/10 REVISED: EMF-2 Diagram 7, 2 - 5 Door Airlock Application FILENAME: EMF-2 Diagram 7.vsd DRAWING No: DRG-EMF-2_07...
  • Page 15 MODE 6 Timer 5 Timer for clearing “walk-aways” dipswitch as shown below: Apply power to door operators, EMF-2, and all Off On connected equipment (ie – strikes, lights, etc). Observe the red Power LED on the unit, which should light. If not, re-confirm proper voltage and/or See diagram 1 for location of dipswitch, connectors, terminal strip connection.
  • Page 16 To have Relay 5 AC/DC L4W 2T7 shadow another Power relay, set dipswitch as shown at right SCALE: NONE DRAWN BY: DGW DATE: 03/24/10 REVISED: 05/04/11 ON ON EMF-2 Diagram 8, 2 Door Mantrap Application FILENAME: EMF-2 Diagram 8.vsd DRAWING No: DRG-EMF-2_08...
  • Page 17 If door (or the door that is already opened) it will keep left , then the EMF-2 will remember a request to that door opened. open and open that door when the other door has re- closed and locked.
  • Page 18 Not used Timer 5 Timer for clearing “walk-aways” Apply power to door operators, EMF-2, and all connected equipment (ie – strikes, lights, etc). Observe the red Power LED on the unit, which should light. If not, re-confirm proper voltage and/or terminal strip connection.
  • Page 19: Technical Data

    7” x 3” x 7/8” defects for 3 years from date of sale. If during the EMF-2m & EMF-1ABM first 3 years the CX-EMF-2 / EMF-2ABM) fails to 12” x 7.5” x 3.75” perform correctly, it may be returned to our factory...