Victron energy BlueSolar MPPT 150/35 Manual

Victron energy BlueSolar MPPT 150/35 Manual

Charge controller
Hide thumbs Also See for BlueSolar MPPT 150/35:

Advertisement

Manual
Handleiding
Manuel
Anleitung
Manual
Användarhandbok
BlueSolar charge controller MPPT 150/35

Advertisement

Table of Contents
loading

Summary of Contents for Victron energy BlueSolar MPPT 150/35

  • Page 1 Manual Handleiding Manuel Anleitung Manual Användarhandbok BlueSolar charge controller MPPT 150/35...
  • Page 3: General Description

    1. General Description 1.1 Charge current up to 35A and PV voltage up to 150V The BlueSolar MPPT 150/35 charge controller is able to charge a lower nominal-voltage battery from a higher nominal voltage PV array. The controller will automatically adjust to a 12V, 24V or a 48V nominal battery voltage.
  • Page 4 1.8 Flexible charge algorithm Fully programmable charge algorithm, and eight preprogrammed algorithms, selectable with a rotary switch. 1.9 Adaptive three step charging The BlueSolar MPPT Charge Controller is configured for a three step charging process: Bulk – Absorption – Float. 1.9.1.
  • Page 5 1.11 Configuring and monitoring - Bluetooth Smart (VE.Direct Bluetooth Smart dongle needed): the wireless solution to set-up, monitor and update the controller using Apple and Android smartphones, tablets or other devices. - Use the VE.Direct to USB cable (ASS030530000) to connect to a PC, a smartphone with Android and USB On-The-Go support (requires additional USB OTG cable).
  • Page 6: Important Safety Instructions

    2. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS - This manual contains important instructions that shall be followed during installation and maintenance. Danger of explosion from sparking Danger of electric shock ● Please read this manual carefully before the product is installed and put into use.
  • Page 7: Installation

    3. Installation WARNING: DC (PV) INPUT NOT ISOLATED FROM BATTERY CIRCUIT CAUTION: FOR PROPER TEMPERATURE COMPENSATION THE AMBIENT CONDITION FOR CHARGER AND BATTERY MUST BE WITHIN 5°C. 3.1. General ● Mount vertically on a non-flammable substrate, with the power terminals facing downwards. Observe a minimum clearance of 10 cm under and above the product for optimal cooling.
  • Page 8 3.3. PV configuration (also see the MPPT Excel sheet on our website) ● Provide a means to disconnect all current-carrying conductors of a photovoltaic power source from all other conductors in a building or other structure. ● A switch, circuit breaker, or other device, either ac or dc, shall not be installed in a grounded conductor if operation of that switch, circuit breaker, or other device leaves the grounded conductor in an ungrounded state while the system remains...
  • Page 9 3.5 Configuration of the controller Fully programmable charge algorithm (see the software page on our website) and eight preprogrammed charge algorithms, selectable with a rotary switch: Suggested battery Absorption Float Equalize dV/dT Type mV/°C 31,8 Gel Victron long life (OPzV) 28,2 27,6 Gel exide A600 (OPzV)
  • Page 10 On all models with software version V 1.12 or higher a binary LED code helps determining the position of the rotary switch. After changing the position of the rotary switch, the LEDs will blink during 4 seconds as follows: Switch Blink position Bulk...
  • Page 11 The charge controller starts a new charge cycle every morning, when the sun starts shining. Default setting: The maximum duration of the absorption period is determined by the battery voltage measured just before the solar charger starts up in the morning: Battery voltage Vb (@start- Maximum absorption time Vb <...
  • Page 12 3.8 Automatic equalization Automatic equalization is default set to ‘OFF’. With the Victron Connect app (see sect 3.9) this setting can be configured with a number between 1 (every day) and 250 (once every 250 days). When automatic equalization is active, the absorption charge will be followed by a voltage limited constant current period (see table in section 3.5).
  • Page 13: Troubleshooting

    4. Troubleshooting Problem Possible cause Solution Reversed PV connection Connect PV correctly Charger does not function Reverse battery Non replacable fuse blown. connection Return to VE for repair Check battery A bad battery connection connection Cable losses too high Use cables with larger cross section Large ambient Make sure that...
  • Page 14: Specifications

    5. Specifications BlueSolar charge controller MPPT 150/35 Battery voltage 12/24/48V Auto Select (36V: manual) Maximum battery current Nominal PV power, 12V 1a,b) 500W (MPPT range 15V to 130V) Nominal PV power, 24V 1a,b) 1000W (MPPT range 30V to 130V) Nominal PV power, 48V 1a,b) 2000W (MPPT range 60V to 130V) Max.
  • Page 15 Figure 1: Power connections...
  • Page 16 Serial number: Version : 06 Date : September 21 , 2018 Victron Energy B.V. De Paal 35 | 1351 JG Almere PO Box 50016 | 1305 AA Almere | The Netherlands General phone : +31 (0)36 535 97 00 E-mail : sales@victronenergy.com...