C2LINX

®
Installation Guide

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the C2LINX and is the answer not in the manual?

Questions and answers

Summary of Contents for Amphenol C2LINX

  • Page 1: C2Linx

    C2LINX ® Installation Guide...
  • Page 2 Amphenol Network Solutions assumes no liability from the application or use of these products. Neither does Amphenol Network Solutions convey any license under its patent rights nor the patent rights of others. This document and the products described herein are subject to change without notice.
  • Page 3: Table Of Contents

    3.4.1 Rack vs. Cabinet ........................12 3.5 Tools and Equipment ........................13 4. C2LINX Chassis Installation ........................13 4.1 Install Mounting Brackets on the C2LINX Chassis ................13 4.2 Installing the Chassis on the Rack ....................14 4.3 C2LINX Opening Doors ........................14 4.3.1 C2LINX Front Door ........................
  • Page 4 9.3 Repackage for Shipment ........................42 9.4 Ordering Replacement Parts ......................42 9.4.1 Replacing a Tray ........................42 9.4.2 Replacing a Door ........................43 9.4.3 Replacing Links ......................... 43 Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ® 509.926.6000 — amphenol-ns.com...
  • Page 5 List of Figures Fig. 1-1: C2LINX 1RU chassis ........................7 Fig. 2-1: C2LINX tray ............................ 8 Fig. 2-2: HD Links ............................9 Fig. 2-3: Chassis wall links ........................... 9 Fig. 2-4: Chassis door........................... 9 Fig. 2-5: Designation label .......................... 10 Fig.
  • Page 6 Fig. 7-4: Alignment of hinge ........................39 Fig. 7-5: Chassis wall link locations ......................40 Fig. 7-6: Locking the door ........................... 40 Fig. 9-1: Removing/replacing the door ....................... 43 Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 7: Introduction

    1. Introduction This installation guide gives directions on: • How to install the C2LINX chassis on either a 19- or 23-inch rack or cabinet • How to install patch modules, patch-and-splice modules, pre-terminated modules, splitter and MPO modules • How to route and secure the fiber optic cable within the chassis Fig.
  • Page 8: Terminology

    2.2 Panel Components 2.2.1 Trays Left and right trays of the C2LINX chassis slide in and out by pulling up and out on the yellow locking handles. This allows easy access to the modules. Each tray holds two modules. Fig. 2-1: C2LINX tray...
  • Page 9: Hd Links

    Chassis doors open toward the center of the chassis for space optimization. They are easy to remove and re- install if necessary. See Section 5 for pre-terminated rear door installation. Fig. 2-4: Chassis door Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 10: Designation Cards

    Fig. 2-6: Mounting brackets 2.3 Panel Module Overview C2LINX modules are interchangeable within the C2LINX trays, allowing for the ability to mix and match different modules and configurations. The following modules are available for C2LINX: •...
  • Page 11: Installation Considerations

    Upon receipt of your order, carefully unpack contents and compare it with the packing list and the order placed. While items described below are a comprehensive list that includes the C2LINX chassis, trays, brackets and doors, the contents of your order may vary.
  • Page 12: Inspection

    Plan the input/output, upward/downward (cable feed) layout of each module and its position in the chassis before beginning C2LINX chassis installation. The C2LINX chassis adapts to standard 19- or 23-inch ETSI racks with EIA, ETSI and WECO spacing and nominal 5½-inch extensions beyond the front rack flange.
  • Page 13: Tools And Equipment

    Fig. 3-1: C2LINX working footprint 3.5 Tools and Equipment Phillips and flat-head screwdrivers are required. No other tools are needed to assemble the C2LINX chassis and corresponding modules. If links need replacement on the chassis, needle-nosed pliers are required to separate the links.
  • Page 14: Installing The Chassis On The Rack

    Two screws per side are used to attach the chassis to the rack. Fig. 4-3: Mounting the bracket to the rack 4.3 C2LINX Opening Doors 4.3.1 C2LINX Front Door Plastic latches are located on the end of each door.
  • Page 15: C2Linx Rear Door

    4.3.2 C2LINX Rear Door Plastic latches are located on the end of each door. 1. Pinch latches together on the doors. 2. Pivot door on the center hinge to open. Fig. 4-5: Rear door 4.4 Chassis Wall Links Chassis wall links attach the side wall of the chassis. Front and rear chassis wall links are not installed to avoid interferences with rail racks or cabinets.
  • Page 16: Designation Labels

    Fig. 4-7: Installing the tray links to trays 4.5 Designation Labels Designation labels are located on each C2LINX door. Designation labels are used to identify adapter fiber jumper information at the front of the panel and connector pigtail fiber information at the rear of the panel.
  • Page 17: Install Designation Labels

    Immediately report any shipping damage, defects or missing parts to Amphenol Network Solutions. Keep all documentation that comes with your shipment. Amphenol Network Solutions is not liable for shipping damage. If the product is damaged, notify the carrier and call Amphenol Network Solutions at 509-926-6000 for further recourse.
  • Page 18: Packaging

    See Pre-Terminated Quick Start Guide if you are adding a C2LINX chassis or fiber. If this is your first installation of C2LINX Pre-Terminated Modules, continue through the full installation of the product.
  • Page 19: Installing Rack Mount Slide Brackets

    NOTE: Do not tighten securely to the rack. This allows easier alignment for chassis to slide into correct position. NOTE: Use two screws per side when attaching the chassis to the rack. Fig. 5-4: Mounting brackets to the rack Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 20: Installing Chassis In Rack

    4. Push the chassis all the way forward. You will hear a click on both sides of the chassis. Ensure tabs have fully engaged. Rear Fig. 5-6: Tab fully engaged showing Fig. 5-7: Chassis set in rack Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ® 509.926.6000 — amphenol-ns.com...
  • Page 21: Releasing Rack Bracket

    3. Repeat on opposite side to fully release chassis from the rack and mounting brackets. 4. Both sides can be done at same time. Depress locking tab Fig. 5-9: Locking tabs Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ® 509.926.6000 — amphenol-ns.com...
  • Page 22: Chassis Wall Links

    (Fig. 5-12). 6. Repeat steps on all right and left trays. Fig. 5-10: Installing chassis wall links Fig. 5-11: Installing tray links to trays Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ® 509.926.6000 — amphenol-ns.com...
  • Page 23: Removing Back Cover And Door

    1. Unscrew the thumbscrew(s) located on the back cover. Fig. 5-12: Removing thumb screws 2. Remove center thumbscrew or nylatch on back cover on rear door. Fig. 5-13: Removing back door and cover thumbscrew(s) Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 24: C2Linx Module Installation

    6. C2LINX Module Installation 6.1 Opening the Tray C2LINX modules can be installed in any position on any tray in the chassis. Take the following steps: 1. Open the door of the chassis by squeezing the latches together. 2. Pull the door toward you.
  • Page 25: Installing A Module

    1. Insert the module into the desired space on the tray. Slightly angle the module and slide it back on the surface of the tray until you hear the module click into place on the tray. Fig. 6-5: Installing a module Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 26: Removing A Module

    10. Using the sticker kit that came with the module, label each port with the corresponding number (Fig. 6-7). 11. Locate adapter designation number on the designation card located on the front door of the C2LINX chassis. Record designation information.
  • Page 27: Fig. 6-7: Labeling The Fiber Ports

    16. Lace cables through the links (Fig. 6.10). 17. Once the cables are routed, return tabs to their lock position by pushing and rotating them so they lock under the locking tab (Fig. 6.10). Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 28: Fig. 6-9: Routing Cable Through The Face Plate

    21. Repeat steps 3-9 from section 6.5 above NOTE: Amphenol Network Solutions requires the use of G.657.A1 fiber and recommends using G.657.A2 bend insensitive 1.6 or 1.2 mm fiber with short boots to further protect the fiber, also LC with low-profile triggers are recommended.
  • Page 29: Adding/Replacing Fiber Jumpers To An Installed Patch Module

    3. Go to the rear of the tray and pull to open. 4. Lift the shuttle up and pull it back as shown. New connection on the cassette Fig. 6-12: Installing a fiber on the shuttle Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ® 509.926.6000 — amphenol-ns.com...
  • Page 30: Fig. 6-13: Connecting The Fiber

    19. Repeat Steps 14-18 if needed. NOTE: After confirming the fiber jumper end is clean, do not wipe the fiber or allow it to touch anything before installing it in the adapter. Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 31: Installing Mpo Modules

    21. Route the fiber on the front of the chassis through the links as shown below. NOTE: Amphenol Network Solutions requires the use of G.657.A1 fiber and recommends using G.657.A2 bend insensitive 1.6 or 1.2 mm fiber with short boots to further protect the fiber, also LC with low-profile triggers are recommended.
  • Page 32: Fig. 6-16: Routing Fibers Through The Links

    18. Route the fiber on the front of the chassis through the links as shown below. NOTE: Amphenol Network Solutions requires the use of G.657.A1 fiber and recommends using G.657.A2 bend insensitive 1.6 or 1.2 mm fiber with short boots to further protect the fiber, also LC with low-profile triggers are recommended.
  • Page 33: Splitter Modules

    NOTE: Use care to maintain bend radius and not damage fibers. 1. Remove top clear cover of the cassette to start the splicing process. C2LINX modules are provided with one meter of pre-terminated 250um pigtails (ribbon or stranded), Kevlar clamp, IFC holder and splice sleeves.
  • Page 34: Fig. 6-17: Opening The Splice Cassette

    Place spliced fiber into splice holder. For stranded fiber, the holder will be offset. For ribbon fiber, the mass fusion splice is centered in the cassette (Fig. 6-18). Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 35: Fig. 6-19: Laying Out Slack Loops

    2. As each fiber is spliced and placed into the splice holder, lay out the slack loops to ensure fibers do not cross over each other. Fig. 6-19: Laying out slack loops 3. Coil the spliced fibers back into the splice cassette. Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 36: Fig. 6-20: Coiling Fiber Into Cassette

    Fig. 6-21: Tuck fiber under fingers 5. Re-install the clear cover on the cassette by pressing on each locking tab. Fig. 6-22: Re-install clear cover Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ® 509.926.6000 — amphenol-ns.com...
  • Page 37: Connecting Fiber Jumpers

    Fiber jumpers enter the C2LINX chassis from the links and plug into the cassette adapters following the designation label number scheme mounted on the front door. 1. Locate adapter designation number on the designation card located on the front door of the C2LINX chassis. Record designation information.
  • Page 38: Seismic Latch Installation

    2. Ensure the hinge and link match the top and bottom views below. Hinge Bottom Fig. 7-2: Alignment of hinge 3. Repeat steps 1-2 with remaining left links. Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ® 509.926.6000 — amphenol-ns.com...
  • Page 39: Fig. 7-3: Right Arm Link

    5. Check that the hinge and link match the top and bottom views below. Hinge Bottom Fig. 7-4: Alignment of hinge 6. Repeat steps 4-5 with remaining right links. Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ® 509.926.6000 — amphenol-ns.com...
  • Page 40: Fig. 7-5: Chassis Wall Link Locations

    4RU (location seventh from the bottom) Fig. 7-5: Chassis wall link locations 8. Place arm into the slot in the door, in every location. Fig. 7-6: Locking the door Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...
  • Page 41: Service

    Although Amphenol Network Solutions includes dust caps with all adapters and connectors, it isn’t always possible to ensure fiber ferrules stay clean. If you need to clean connectors and adapters, Amphenol Network Solutions recommends a commercially available system or solution.
  • Page 42: Customer Service And Ordering Information

    Contact your Amphenol Network Solutions equipment distributor or call Amphenol Network Solutions Support to talk with a Customer Service Representative. Amphenol Network Solutions will repair or replace defective products within the limits of the warranty. See Section 9.3, Repackage for Shipment.
  • Page 43: Replacing A Door

    NOTE: Make sure left links are used on the left side and right links are used on the right side. The left/right designation is on the underside of the link. Amphenol Network Solutions C2LINX All rights reserved. 04.13.20 150717 A0 ®...