Download Print this page

Program Settings - Nibe POOL 40 Installer Manual

Pool heating for s1155; s1255; smo s40; smo s40; f1245; f1155; f1245; f1345; f1355; smo 40
Hide thumbs Also See for POOL 40:

Advertisement

Available languages

Available languages

Program settings

Program setting of POOL 40 can be performed via the
start guide or directly in the menu system.
START GUIDE
The start guide appears at first start-up after heat pump
installation, but can also be found in menu 7.7.
MENU SYSTEM
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
MENU 7.2.1 - ADD/REMOVE ACCESSORIES
Here, you state which accessories are installed for the
compatible product.
To identify connected accessories automatically, select
"Search for accessories". It is also possible to select ac-
cessories manually from the list.
MENU 7.2.17 - POOL
Activate/Deactivate Pool
start temp
Setting range: 5,0 – 80,0 °C
stop temperature
Setting range: 5,0 – 80,0 °C
Max. number of compressors
Setting range: 1-18
Desired charge power
Setting range: 1-100 kW
Activate/Deactivate: Here, you activate or deactivate
pool heating.
Start and Stop temperature: Here, you set the start and
stop temperature of pool heating.
Max. number of compressors: Here, you select the
number of compressors that will heat the pool.
Desired charge power: Here, you select the desired
charge power to the pool.
NOTE
The same settings can be made for Pool 2.
Caution
The start temperature cannot be set to a value
that is higher than the stop temperature.
22
MENU 7.1.2.1 - OPERATING MODE HEATING
MEDIUM PUMP GP1
Operating status
Alternative: Auto, intermittent
Auto: The heating medium pump runs according to the
current operating mode for a compatible product.
Intermittent: The heating medium pump starts approx.
20 seconds before and stops 20 seconds after the
compressor.
MENU 7.1.2.2 - PUMP SPEED HEATING
MEDIUM GP1
Make settings here for the heating medium pump's
speed in the current operating mode, for example in
heating or hot water operation. Which operating modes
can be changed depends on which accessories are
connected.
Heating, auto
Alternative: on/off
Heating, auto: Here, you set whether the heating medi-
um pump is to be regulated automatically or manually.
Heating, manual: If you have opted to control the heating
medium pump manually, you set the desired pump
speed here.
Caution
Also see the Installer manual for the product
that POOL 40 will be connected to.
POOL 40 | GB

Hide quick links:

Advertisement

loading

This manual is also suitable for:

S1155S1255Smo s40F1145F1245F1155 ... Show all