Pilz PNOZ s22 Series Operating Manual

Pilz PNOZ s22 Series Operating Manual

Safety relays

Advertisement

PNOZ s22
}
Safety relays
Operating Manual-22170-EN-04

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PNOZ s22 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Pilz PNOZ s22 Series

  • Page 1 PNOZ s22 Safety relays Operating Manual-22170-EN-04...
  • Page 2 Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
  • Page 3: Table Of Contents

    Contents Introduction Validity of documentation Using the documentation Definition of symbols Safety Intended use Safety regulations Safety assessment Use of qualified personnel Warranty and liability Disposal For your safety Unit features Safety features Block diagram/terminal configuration Function description Installation Wiring Preparing for operation Operation Status indicators...
  • Page 4 Contents Permitted operating height Remove plug-in terminals Order reference EC declaration of conformity Operating Manual PNOZ s22 22170-EN-04...
  • Page 5: Introduction

    PNOZ s22 Introduction Validity of documentation This documentation is valid for the product PNOZ s22. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product. Using the documentation This document is intended for instruction.
  • Page 6: Safety

    PNOZ s22 INFORMATION This gives advice on applications and provides information on special fea- tures. Safety Intended use The unit meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1. The con- tact expansion module is used to increase the number of instantaneous safety contacts available on a base unit.
  • Page 7: Safety Regulations

    PNOZ s22 Safety regulations Safety assessment Before using a device it is necessary to perform a safety assessment in accordance with the Machinery Directive. Functional safety is guaranteed for the product as a single component. However, this does not guarantee the functional safety of the overall plant/machine. In order to achieve the re- quired safety level for the overall plant/machine, define the safety requirements for the plant/machine and then define how these must be implemented from a technical and organ- isational standpoint.
  • Page 8: For Your Safety

    PNOZ s22 For your safety The unit meets all the necessary conditions for safe operation. However, please note the following: Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120 VDC) are present on the unit, connected control elements and sensors must have a rated insulation voltage of at least 250 V.
  • Page 9: Block Diagram/Terminal Configuration

    PNOZ s22 Block diagram/terminal configuration *Safe separation from non-marked area in accordance with EN 60947-1, 6 kV, basic insula- tion between all safety contacts. Function description Dual-channel operation and supply voltage via PNOZsigma connector 3 safety contacts and 1 auxiliary contact each; these can be controlled separately Installation Connect the contact expansion block to the PNOZ s30 or base unit PNOZ mm0.1p/ PNOZ mm0.2p...
  • Page 10: Wiring

    PNOZ s22 Wiring Please note: Information given in the "Technical details [ 12]" must be followed. The wiring guidelines in the base units' operating instructions must be taken into ac- count. Outputs 13-14, 23-24, 33-34 are safety contacts; output 41-42 is an auxiliary contact (e.g.
  • Page 11: Operation

    PNOZ s22 Operation When the relay outputs are switched on, the mechanical contact on the relay cannot be tested automatically. Depending on the operational environment, measures to detect the non-opening of switching elements may be required under some circumstances. When the product is used in accordance with the European Machinery Directive, a check must be carried out to ensure that the safety contacts on the relay outputs open correctly.
  • Page 12: Dimensions In Mm

    PNOZ s22 Dimensions in mm *with spring-loaded terminals Technical details General 750132 751132 CCC, EAC (Eurasian), TÜV, cU- CCC, EAC (Eurasian), TÜV, cU- Approvals Lus Listed Lus Listed Electrical data 750132 751132 Supply voltage Voltage tolerance -15 %/+20 % -15 %/+20 % Supply voltage Voltage 24 V...
  • Page 13 PNOZ s22 Relay outputs 750132 751132 Utilisation category of safety con- tacts AC1 at 240 V 240 V Min. current 0,01 A 0,01 A Max. current Max. power 1500 VA 1500 VA DC1 at 24 V 24 V Min. current 0,01 A 0,01 A Max.
  • Page 14 PNOZ s22 Relay outputs 750132 751132 External contact fuse protection, safety contacts In accordance with the standard EN 60947-5-1 EN 60947-5-1 Max. melting integral 66 A²s 66 A²s Blow-out fuse, quick Blow-out fuse, slow Blow-out fuse, gG Circuit breaker 24V AC/DC, characteristic B/C External contact fuse protection, auxiliary contacts...
  • Page 15 PNOZ s22 Environmental data 750132 751132 Vibration In accordance with the standard EN 60068-2-6 EN 60068-2-6 Frequency 10 - 55 Hz 10 - 55 Hz Amplitude 0,35 mm 0,35 mm Airgap creepage In accordance with the standard EN 60947-1 EN 60947-1 Overvoltage category Pollution degree Rated insulation voltage...
  • Page 16: Safety Characteristic Data

    PNOZ s22 Where standards are undated, the 2017-01 latest editions shall apply. The values for conventional thermal current stated in the technical details apply when the contacts from Ext.1/O0 and Ext.2/O1 are under load simultaneously. Conventional thermal current when either the contacts from Ext.1/O0 or the contacts from Ext.2/O1 are under load: Number of contacts in total...
  • Page 17: Supplementary Data

    PNOZ s22 Supplementary data CAUTION! It is essential to consider the relay's service life graphs. The relay outputs' safety-related characteristic data is only valid if the values in the service life graphs are met. The PFH value depends on the switching frequency and the load on the relay output. If the service life graphs are not accessible, the stated PFH value can be used irrespective of the switching frequency and the load, as the PFH value already considers the relay's B10d value as well as the failure rates of the other components.
  • Page 18 PNOZ s22 Switching current (A) Fig.: Service life graphs at 110 VDC Example Inductive load: 0.2 A Utilisation category: AC15 Contact service life: 1 000 000 cycles Provided the application to be implemented requires fewer than 1 000 000 cycles, the PFH value (see Technical details [ 12]) can be used in the calculation.
  • Page 19 PNOZ s22 Permitted operating height The values stated in the technical details apply to the use of the device in operating heights up to max. 2000 m above sea level. When used in greater heights, constraints have to be taken into account: Permitted maximum operating height 5000 m Reduction of rated insulation voltage and rated impulse withstand voltage for applica- tions with safe separation:...
  • Page 20 European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost- fildern, Germany Operating Manual PNOZ s22...
  • Page 21 Back cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95600621 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...