Burner Set-Up Chart - Riello F20 Installation, Use And Maintenance Instructions

With hydraulic jack
Table of Contents

Advertisement

Available languages

Available languages

BURNER SET-UP CHART

NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow the
installation and set-up instructions supplied with the heating unit, as settings will differ from those shown
in this manual.
1
Actual
Firing
Rate ± 5%
GPH
Kg/h
3.50
11.3
4.00
12.9
4.65
15.0
5.30
17.1
6.00
19.4
6.40
20.7
NOZZLES RECCOMANDED:
Monarch R-PLP, Delavan W-B, Danfoss S-B, Steinen SS-S, Hago P.
NOTE:
A 45° degree nozzle is suggested, however, a 60° degree nozzle may be used in cases where the flame is
unstable at light-off when operated at low ambient temperatures.
2902453
2
Nozzle
Size
GPH
PSI
2.50 x 45° / 60°
190
3.00 x 45° / 60°
178
3.50 x 45° / 60°
178
4.00 x 45° / 60°
178
4.50 x 45° / 60°
178
5.00 x 45° / 60°
165
3
4
Pump
Turbulator
Pressure
Setting
bar
13.0
0.0
12.0
1.0
12.0
2.0
12.0
3.0
12.0
4.0
11.4
5.0
10
5
Air Damper
Setting
Low Fire
Main Flame
2.3
2.8
2.5
3.2
2.8
3.7
3.2
4.5
3.5
5.0
3.8
6.0
GB